| 2022-09-01 10:53:51 | 1ST REVIEW FMC | | | PERMIT: 22080216 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE USE OF SPACE FOR EACH TENANT SPACE. FBC | | | 107.3.5 | | | | | | 2) PROVIDE A DEMOLITION DRAWING FOR THE MECHANICAL | | | SYSTEMS FOR EACH TENANT SPACE. FBC 107.3.5 | | | | | | 3) PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE USE OF | | | SPACE FROM FMC TABLE 403.3.1.1. FMC 403.3.1.1 | | | | | | 4) REVISE THE MECHANICAL DRAWINGS TO INCLUDE THE | | | OUTDOOR AIR DUCT TO THE MECHANICAL SYSTEM AND THE | | | SHUTOFF DAMPERS REQUIRED. FEC C403.2.4.3 | | | | | | 5) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR EACH MECHANICAL SYSTEM. FEC C403.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|