| Date |
Text |
| 2022-10-06 10:59:59 | 10/06/22 RECEIVED EMAIL FROM ELIZABETH TUKE (OWNER) TO |
| | APPROVE BUILDING WITH PROVISO. JG. |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO. |
| | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS): |
| | 1- LAUNDRY ROOM ADDITION: PROVIDE COMPLETE ROOF FRAMING |
| | PLAN. SPECIFY ALL STRUCTURAL FRAMING MEMBERS AND |
| | CONNECTORS. |
| | NOTE: THERE ARE NO CITY RECORDS/PERMITS FOR CARPORT |
| | ADDITION AT THIS AREA. PLANS SHOW THIS CARPORT TOO |
| | CLOSE TO THE PROPERTY LINE. NEED ZONING AND BUILDING |
| | APPROVAL. CARPORT WILL NEED TO COMPLY WITH ZONING |
| | SETBACKS AND BUILDING FIRE RESISTANCE CONSTRUCTION |
| | REQUIREMENTS OF TABLE R302.1 FBC-RESIDENTIAL. IN |
| | ADDITON, NEED TO SHOW HOW RAIN WATER IS DIVERTED SO IT |
| | DOESN'T FALL INTO NEIGHBOR'S PROPERTY. BE AWARE. |
| | CARPORT MAY NEED TO BE REMOVED. |
| | 2- CRAWL SPACE: NEED ACCESS. SHOW SIZE & LOCATION. |
| | 3- PROVIDE COMPLETE DETAILS/SPECS FOR THE CONSTRUCTION |
| | OF THE BOXED COLUMNS SUPPORTING THE BALCONY GUARDRAIL. |
| | SPECIFY ALL FRAMING MEMBERS & CONNECTORS. |
| | 4- ROOF INSULATION: SPECIFY INSULATION TYPE SHOWING |
| | COMPLIANCE WITH THE UNVENTED ATTIC SEC. R806.5 |
| | FBC-RESIDENTIAL. |
| | NOTE: IF SPRAY FOAM INSULATION, THEN PROVIDE ICC |
| | EVALUATION REPORT. ARCHITECT TO APPROVE REPORT PRIOR TO |
| | SUBMITTAL. |
| | 5- ROOF SHEATHING: REVISE NAILING SPACING TO COMPLY |
| | WITH TABLE R803.2.3.1 FBC-RESIDENTIAL FOR ALL ROOF |
| | ZONES. |
| | 6- PROVIDE PRODUCT APPROVAL FOR: |
| | A)INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| | B)SINGLE HUNG WINDOWS. |
| | C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | D) NEW LOUVERED SHUTTERS AS SPECIFIED ON PLANS. AND, |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| | SAMPLE. |
| | E)AIR HANDLER UNIT EXTERIOR DOOR AS SHOWN ON PLANS. |
| | F)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL). |
| | G)HARDIE BOARD SIDING AS SPECIFIED ON PLANS. |
| | H)ROOF SHINGLES. |
| | I)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| | J) BALCONY UNDERLAYMENT SPECIFIED ON PLANS FOR PROPOSED |
| | FINISH FLOOR. |
| | 7- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS. |
| | 8- REPLACEMENT OF WINDOWS. WINDOW FALL PROTECTION SHALL |
| | BE PROVIDED ON 2ND FLOOR WINDOWS WHERE WINDOW SILL IS |
| | LESS THAN 24" ABOVE THE FINISHED FLOOR . SEC. R312.2 |
| | FBC RESIDENTIAL. |
| | NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND |
| | FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL |
| | PROTECTION IF REQUIRED. |
| | |