| 2022-09-19 12:15:07 | 2ND REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22080208 | | | 9/19/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) P1: THE REVISED ISOMETRIC DOES NOT APPEAR INDICATE | | | PROPER VENTING OF THE FIRST FLOOR FIXTURES: | | | | | | A) PROVIDE A VENT FOR THE BAR SINK- SEC P3106.1 FBC | | | RES. THE VENT CAN BE AN AAV AS AN ALTERNATIVE TO A VENT | | | TO OPEN AIR- SECS. P3104.1 & P3114.3 | | | | | | B) FOR CLARITY, PLEASE IDENTIFY THE LOCATIONS OF THE | | | WASHING MACHINE AND POWDER ROOM WATER CLOSET FIXTURE | | | DRAINS AND VENTS. TYPICALLY HORIZONTAL WET VENTS ARE | | | USED FOR BATHROOMS HOWEVER IT APPEARS THE INTENTION IS | | | EITHER TO VENT THE LAUNDRY SINK COMMONLY WITH THE | | | LAVATORY, OR A CIRCUIT VENT IS BEING USED FOR THE | | | LAVATORY, LAUNDRY SINK AND WASHING MACHINE FIXTURE | | | DRAINS- PLEASE SEE SECS. P3107.1 & P3110.1 FBC RES. | | | | | | C) THE VENT HEADER ABOVE THE POWDER ROOM AND LAUNDRY | | | NEEDS A VENT TO OPEN AIR CONNECTION- SEC. P3104.1 FBC | | | RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|