Plan Review Notes
Plan Review Notes For Permit 22080208
Permit Number 22080208
Review Stop B
Sequence Number 2
Notes
Date Text
2022-10-04 14:57:13RESIDENTIAL R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22080208
 234 EDGEWOOD DR. (MAIN HOUSE)
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
 1- OK.
 2- OK.
 3- OK.
 4- OK.
 5- OK.
  
 ORIGINAL COMMENT:
 6- CRAWL SPACE VENT TO COMPLY WITH SEC. R408
 FBC-RESIDENTIAL. SPECIFY LOCATION, ACCESS SIZE, MIN.
 SIZE OF VENT, ETC. NOTE: THIS APPLIES TO KITCHEN
 ADDITION AND LAUNDRY ADDITION.
  
 RESPONSE:
 NEED ACCESS TO THE CRAWL SPACE. SEE SEC. R408.4
 FBC-RESIDENTIAL.
  
 7- A)OK.
  
 ORIGINAL COMMENT:
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE COLUMNS SUPPORTING THE BALCONY
 GUARDRAIL. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 DETAILS/SPECS NO PROVIDED. THIS COMMENT IS FOR BOXED
 COLUMNS SHOWN ON EXTERIOR ELEVATIONS FOR NEW BALCONY
 GUARDRAIL.
  
 8- OK.
  
 ORIGINAL COMMENT:
 9- ROOF VENTILATION: SPECIFY ROOF CROSS VENTILATION AS
 REQUIRED BY SEC. R806 FBC-RESIDENTIAL. SPECIFY VENTS
 SIZE AND LOCATION.
  
 RESPONSE:
 PARTIALLY COMPLIED. WALL SECTION 1/A3.1 SPECIFIES R-30
 INSULATION UNDER ROOF SHEATHING. CLEARLY SPECIFY
 INSULATION TYPE SHOWING COMPLIANCE WITH THE UNVENTED
 ATTIC SEC. R806.5 FBC-RESIDENTIAL.
 NOTE: IF SPECIFYING SPRAY FOAM INSULATION, THEN PROVIDE
 ICC EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE
  
 ORIGINAL COMMENT:
 10- ROOF SHEATHING: REVISE ROOF SHEATHING NAILING
 SPECIFICATIONS TO COMPLY WITH NEW 2020 FBC-RESIDENTIAL
 SPECIFICATIONS. REVISED TYPE, SIZE AND SPACING. NOTE:
 NEED TO USE RING SHANK NAILS. ROOF SHEATHING NEEDS TO
 BE NAILED AT 4 INCHES O.C. IN THE FIELD AND EDGES AS
 REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1
 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 RESPONSE:
 NOTE #5 OF WIND DESIGN TABLE ON SHEET S2 ONLY SPECIFY
 NAILS AT 4"O.C. FOR EAVES AND OVERHANGS. THIS DOESN'T
 COMPLY WITH THE REQUIREMENTS OF TABLE R803.2.3.1
 FBC-RESIDENTIAL. THERE ARE MORE ZONES REQUIRED TO BE
 NAILED AT 4"0.C. REVISE AS REQUIRED.
  
 11- OK.
  
 ORIGINAL COMMENT:
 12- LAUNDRY ROOM REAR PORCH: MISSING ROOF FRAMING PLAN.
 SPECIFY ALL STRUCTURAL FRAMING MEMBERS AND CONNECTORS
 AT EACH END. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES THERE IS AN EXISTING
 ROOF. A RESEARCH WAS DONE TO VERIFY EXISTING ROOF. THE
 RESEARCH WAS DONE BECAUSE PLANS SUBMITTED SHOW AN
 EXISTING CARPORT THAT IS SITTING RIGHT ON THE PROPERTY
 LINE. ACCORDING TO CITY RECORDS, THERE ARE NO PERMITS
 FOR THE CONSTRUCTION OF THIS CARPORT. ALSO, LOOKING AT
 THE PROPERTY APPRAISER AERIAL MAPS, IT WAS FOUND THAT
 THE 2009 AERIAL MAP DOESN'T SHOW THE CARPORT, BUT THE
 2012 AERIAL MAP DOES SHOW THE CARPORT. THERE ARE NO
 PERMIT APPLICATIONS SUBMITTED TO THE CITY DURING THIS
 TIME.
 BASED ON THIS, A PERMIT IS REQUIRED FOR THE CARPORT
 CONSTRUCTION.
 NOTE: COORDINATE WITH ZONING FOR REQUIRED SETBACKS. IT
 LOOKS LIKE IT MAY NOT BE ALLOWED BY ZONING. IF THE
 CARPORT IS NOT ALLOWED, THEN IT NEEDS TO BE REMOVED.
  
 13- OK.
  
 14- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
 B)SINGLE HUNG WINDOWS.
 C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 D) NEW LOUVERED SHUTTERS AS SPECIFIED ON PLANS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
 E)AIR HANDLER UNIT EXTERIOR DOOR.
 F)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 G)HARDIE BOARD SIDING AS SPECIFIED ON PLANS.
 H)ROOF SHINGLES. PLANS ARE NOT CLEAR ON ROOFING
 MATERIAL.
 I)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 J) BALCONY UNDERLAYMENT SPECIFIED ON PLANS FOR PROPOSED
 FINISH FLOOR.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 NEW COMMENT BASED ON ADDITIONAL SCOPE OF WORK SUBMITTED
 ON PLANS:
 16-REPLACEMENT OF ALL WINDOWS. WINDOW FALL PROTECTION
 SHALL BE PROVIDED ON SECOND FLOOR WINDOWS WHERE THE TOP
 OF THE WINDOW SILL OF AN OPERABLE WINDOW IS LOCATED
 LESS THAN 24" ABOVE THE FINISHED FLOOR . SEC. R312.2
 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND
 FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL
 PROTECTION IF REQUIRED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION