| Plan Review Notes For Permit 22080208 |
| Permit Number |
22080208 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-15 10:09:23 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22080208 | | | 8/15/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) P1: THE LAUNDRY TUB AND WASHING MACHINE FIXTURE | | | DRAINS SHALL NOT CONNECT TO THE HORIZONTAL WET VENT FOR | | | THE POWDER ROOM- SEC. 3108.1 FBC RES. PLEASE PROVIDE A | | | COMPLETE SANITARY RISER DRAWING THAT SHOWS THE | | | CONNECTIONS OF THE NEW 3-INCH BRANCH DRAIN AT WET BAR, | | | AND THE 3-INCH DOWN PIPE FROM THE 2ND FLOOR- SEC. | | | 107.3.5.3 WPB. | | | | | | 2) P1: PLEASE SHOW THE LOCATION OF THE REQUIRED TWO-WAY | | | CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND | | | SEWER LINE- SECS. P3005.2.3 & P3005.2.8 FBC RES. | | | | | | 3) P1: PLEASE SHOW THE LOCATION OF THE EXISTING OR NEW | | | WATER HEATER- SEC. P2801.1 FBC RES. CLARIFY IF IT IS | | | GAS OR ELECTRIC, STORAGE OR TANKLESS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|