2022-08-15 10:09:231ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22080208
 8/15/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P1: THE LAUNDRY TUB AND WASHING MACHINE FIXTURE
 DRAINS SHALL NOT CONNECT TO THE HORIZONTAL WET VENT FOR
 THE POWDER ROOM- SEC. 3108.1 FBC RES. PLEASE PROVIDE A
 COMPLETE SANITARY RISER DRAWING THAT SHOWS THE
 CONNECTIONS OF THE NEW 3-INCH BRANCH DRAIN AT WET BAR,
 AND THE 3-INCH DOWN PIPE FROM THE 2ND FLOOR- SEC.
 107.3.5.3 WPB.
  
 2) P1: PLEASE SHOW THE LOCATION OF THE REQUIRED TWO-WAY
 CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND
 SEWER LINE- SECS. P3005.2.3 & P3005.2.8 FBC RES.
  
 3) P1: PLEASE SHOW THE LOCATION OF THE EXISTING OR NEW
 WATER HEATER- SEC. P2801.1 FBC RES. CLARIFY IF IT IS
 GAS OR ELECTRIC, STORAGE OR TANKLESS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  