| 2023-01-13 15:10:39 | 3RD REVIEW FMC | | | PERMIT: 22080183 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THIS REVIEWER DOES NOT SEE THE MECHANICAL EQUIPMENT | | | SIZING CALCULATIONS ASKED FOR IN THE PREVIOUS REVIEW | | | CYCLES. PLEASE PROVIDE THEM. | | | | | | 2) PLEASE UNDERSTAND, YOU ARE REQUIRED TO PROVIDE THE | | | OUTDOOR AIR CALCULATIONS BASED ON THE OCCUPANCY | | | CLASSIFICATION FOR EACH USE OF SPACE AND THIS IS | | | CALCULATED BY OCCUPANT DENSITY. ALL FROM TABLE | | | 403.3.1.1. THERE ARE NO HOUSE LIMIT RULES. PROVIDE A | | | CALCULATION FOR EACH USE OF SPACE BASED ON THE MOST | | | SIMILAR OCCUPANCY CLASSIFICATION AND THE OCCUPANT | | | DENSITY IN THE TABLE 403.3.1.1.FMC 403.3.1.1 AND TABLE | | | 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|