Plan Review Notes
Plan Review Notes For Permit 22080183
Permit Number 22080183
Review Stop P
Sequence Number 2
Notes
Date Text
2022-11-02 09:33:34FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080183 4065 N HAVERHILL RD #B7
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A SEPARATE PERMIT FOR THE SOLIDS INTERCEPTOR IS
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. A
 SEPARATE PERMIT IS REQUIRED HOWEVER A REVIEW OF THE
 SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY
 ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS
 EXAMINER AT [email protected] AND RYAN BROWN, CHIEF
 PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH
 THE PERMIT NUMBER(S).
  
 1. THE TMV HAS BEEN REMOVED FROM REVISED P-1/HIGH TEMP
 DOMESTIC WATER HEATER DETAIL. PROVIDE A TEMPERATURE
 ACTUATED MIXING VALVE COMPLYING WITH ASSE 1017 BETWEEN
 THE WATER HEATERS AND THE HOT WATER DISTRIBUTION SYSTEM
 AS REQUIRED BY FBC PL 607.1.1 AND 613.1.
  
 2. SOLIDS INTERCEPTOR: THE PLANS ARE UNCLEAR AS TO
 WHETHER THE UNIT IS IN AN AREA SUBJECT TO
 AUTOMOTIVE/HEAVY TRAFFIC. PER WPB FBC 107.2.1, CLARIFY.
 PER FBC PL 305.7 & 1003.10, PLEASE INDICATE ON THE
 P-1/SOLIDS INTERCEPTOR SPECIFICATION OPTION C24-HP FOR
 H20 LIDS IF APPLICABLE.
 DESIGNER RESPONSE IS THE UNIT IS NOT SUBJECT TO
 AUTOMOTIVE/HEAVY TRAFFIC
 NEW COMMENT: PLEASE INDICATE ON THE PLANS
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  