| 2022-11-02 09:33:34 | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22080183 4065 N HAVERHILL RD #B7 |
| | |
| | 2ND REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A SEPARATE PERMIT FOR THE SOLIDS INTERCEPTOR IS |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. A |
| | SEPARATE PERMIT IS REQUIRED HOWEVER A REVIEW OF THE |
| | SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED. |
| | AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY |
| | ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS |
| | EXAMINER AT [email protected] AND RYAN BROWN, CHIEF |
| | PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH |
| | THE PERMIT NUMBER(S). |
| | |
| | 1. THE TMV HAS BEEN REMOVED FROM REVISED P-1/HIGH TEMP |
| | DOMESTIC WATER HEATER DETAIL. PROVIDE A TEMPERATURE |
| | ACTUATED MIXING VALVE COMPLYING WITH ASSE 1017 BETWEEN |
| | THE WATER HEATERS AND THE HOT WATER DISTRIBUTION SYSTEM |
| | AS REQUIRED BY FBC PL 607.1.1 AND 613.1. |
| | |
| | 2. SOLIDS INTERCEPTOR: THE PLANS ARE UNCLEAR AS TO |
| | WHETHER THE UNIT IS IN AN AREA SUBJECT TO |
| | AUTOMOTIVE/HEAVY TRAFFIC. PER WPB FBC 107.2.1, CLARIFY. |
| | PER FBC PL 305.7 & 1003.10, PLEASE INDICATE ON THE |
| | P-1/SOLIDS INTERCEPTOR SPECIFICATION OPTION C24-HP FOR |
| | H20 LIDS IF APPLICABLE. |
| | DESIGNER RESPONSE IS THE UNIT IS NOT SUBJECT TO |
| | AUTOMOTIVE/HEAVY TRAFFIC |
| | NEW COMMENT: PLEASE INDICATE ON THE PLANS |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | |