Plan Review Notes
Plan Review Notes For Permit 22080183
Permit Number 22080183
Review Stop M
Sequence Number 2
Notes
Date Text
2022-11-08 13:36:261ST REVIEW FMC
 PERMIT: 22080183
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ASKED
 FOR IN THE 1ST REVIEW CYCLE WAS NOT SUBMITTED THIS
 CYCLE. PLEASE SUBMIT THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS.
  
 2) PROVIDE THE CORRECT OUTDOOR AIR CALCULATIONS FOR A
 COMMERCIAL LAUNDRY. TABLE 403.3.1.1 CLEARLY PROVIDES
 THE OCCUPANT LOAD AND THE CFM???S PER PERSON BASED ON
 THAT OCCUPANT COUNT. THE ENTIRE SPACE IS A COMMERCIAL
 LAUNDRY. PLEASE USE THE ENTIRE NET SQUARE FOOTAGE FOR
 THE COMMERCIAL LAUNDRY REQUIRED OUTDOOR AIR
 CALCULATIONS. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 3) PLEASE SHOW THE REQUIRED DUCT DETECTORS IN THE
 SUPPLY SIDE OF THE MECHANICAL DUCT SYSTEMS. FMC 606.2.2
  
 1ST REVIEW FMC
 PERMIT: 22080183
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ASKED
 FOR IN THE 1ST REVIEW CYCLE WAS NOT SUBMITTED THIS
 CYCLE. PLEASE SUBMIT THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS.
  
 2) PROVIDE THE CORRECT OUTDOOR AIR CALCULATIONS FOR A
 COMMERCIAL LAUNDRY. TABLE 403.3.1.1 CLEARLY PROVIDES
 THE OCCUPANT LOAD AND THE CFM???S PER PERSON BASED ON
 THAT OCCUPANT COUNT. THE ENTIRE SPACE IS A COMMERCIAL
 LAUNDRY. PLEASE USE THE ENTIRE NET SQUARE FOOTAGE FOR
 THE COMMERCIAL LAUNDRY REQUIRED OUTDOOR AIR
 CALCULATIONS. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 3) PLEASE SHOW THE REQUIRED DUCT DETECTORS IN THE
 SUPPLY SIDE OF THE MECHANICAL DUCT SYSTEMS. FMC 606.2.2
  
 4) PLEASE SUBMIT A DRYER EXHAUST DUCT DRAWING THAT WILL
 INCLUDE THE SUBMITTED DRYER SPECS INCLUDING THE MAX.
 AIR FLOW AND MAKE-UP AIR. THE DRYER MANUALS SUBMITTED
 DO NOT REFERENCE THE HTT30, HYY45 OR HT075. PLEASE
 PROVIDE DOCUMENTS WITH THESE MODELS IDENTIFIED. THE M-2
 SHEET SPECS OUT A 4INCH DRYER DUCT FOR A SINGLE DRYER
 WITH A FLEX DUCT FOR THE TRANSITION DUCT. PAGE 35 OF
 THE DRYER SPECS. SUBMITTED INDICATES A SINGLE EXHAUST
 DUCT FOR THE DRYERS WOULD BE AN 8 INCH DUCT. PLEASE USE
 THE SPECS FOR THE DRYERS INCLUDING THE MAX. DISTANCE
 AND PROVIDE A DRYER EXHAUST DRAWING FOR THIS LAUNDRY.
 FMC 504.9
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  