Plan Review Notes
Plan Review Notes For Permit 22080183
Permit Number 22080183
Review Stop G
Sequence Number 2
Notes
Date Text
2022-10-31 15:47:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080183 4075 N HAVERHILL RD
  
 GAS COMMENTS: DENIED
  
 1. COMPLIED
  
 2. COMPLIED
  
 3. SECOND REQUEST: P-3/GAS RISER: REGULATOR AT METER
 REDUCES PRESSURE TO 7 INCHES WATER COLUMN; SIZING
 CALCULATIONS ARE BASED ON FBC FG TABLE 402.4(5) 2
 PSI/1PD/6SG. PER WPB FBC 107.2.1, PLEASE CLARIFY AND
 RECONCILE.
 NEW COMMENT: NOTE FOR REGULATOR AT METER REDUCES
 PRESSURE TO 7 INCHES WATER COLUMN HAS BEEN ELIMINATED;
 SIZING CALCULATIONS ARE STILL BASED ON FBC FG TABLE
 402.4(5) 2 PSI/1PD/6SG INDICATING A 2 PSI SYSTEM.
 ***CONFIRM ON THE PLAN 2 PSI SYSTEM OR LESS THAN 2PSI
 SYSTEM
 ***IF LESS THAN 2 PSI SYSTEM, PROVIDE A SIZING TABLE
 SELECTED FROM FBC FG 402.4
 ***IF A 2PSI SYSTEM IS REQUIRED FOR DISTRIBUTION, THEN
 SPECIFY AND PROVIDE MP REGULATORS FOR FINAL
 CONNECTIONS. PROVIDE SIZING TABLE (FROM FBC FG 402.4)
 FOR REDUCED PRESSURE PIPING AND MAXIMUM DEVELOPED
 LENGTH OF REDUCED PRESSURE SYSTEM(S) FROM MP REGULATOR
 TO FINAL CONNECTIONS. SHOW LOCATIONS OF MP REGULATORS.
  
 4. COMPLIED
  
 5. COMPLIED
  
 6. COMPLIED
  
 7. COMPLIED
  
 8. SECOND REQUEST:P-1/TANKLESS GAS WATER HEATER DETAIL
 INDICATES A CONCENTRIC VENT WITH SINGLE POINT
 CONNECTION FOR SINGLE HEATER. SCHEDULED NAVIEN NPE-240A
 AND P-1/HIGH TEMP DOMESTIC WATER HEATER DETAIL REQUIRES
 DEDICATED COMBUSTION AIR INLET AND EXHAUST OUTLET.
 REFER TO NAVIEN COMMON VENT SYSTEM INSTALLATION MANUAL.
 UPDATED DETAIL SHOWS A CONCENTRIC VENT MANIFOLD WITH
 SINGLE POINT CONNECTION FOR EACH OF THE THREE WATER
 HEATERS.
 NAVIEN COMMON VENT SYSTEM INSTALLATION MANUAL FOR
 SCHEDULED WATER HEATERS REQUIRES A DEDICATED INTAKE
 MANIFOLD AND A DEDICATED EXHAUST MANIFOLD. PER FBC FG
 503.4, PROVIDE VENT SYSTEM IN ACCORDANCE WITH
 MANUFACTURER DIRECTIONS.
  
 PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE THE
 FOLLOWING:
 ***A) A DETAIL THAT PROPERLY ADDRESSES THE VENTING OF
 THE THREE UNITS.
 ***B) SIZE(S) AND MATERIAL SPECIFICATION FOR VENTS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  