| Date |
Text |
| 2022-10-31 15:47:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22080183 4075 N HAVERHILL RD |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | 1. COMPLIED |
| | |
| | 2. COMPLIED |
| | |
| | 3. SECOND REQUEST: P-3/GAS RISER: REGULATOR AT METER |
| | REDUCES PRESSURE TO 7 INCHES WATER COLUMN; SIZING |
| | CALCULATIONS ARE BASED ON FBC FG TABLE 402.4(5) 2 |
| | PSI/1PD/6SG. PER WPB FBC 107.2.1, PLEASE CLARIFY AND |
| | RECONCILE. |
| | NEW COMMENT: NOTE FOR REGULATOR AT METER REDUCES |
| | PRESSURE TO 7 INCHES WATER COLUMN HAS BEEN ELIMINATED; |
| | SIZING CALCULATIONS ARE STILL BASED ON FBC FG TABLE |
| | 402.4(5) 2 PSI/1PD/6SG INDICATING A 2 PSI SYSTEM. |
| | ***CONFIRM ON THE PLAN 2 PSI SYSTEM OR LESS THAN 2PSI |
| | SYSTEM |
| | ***IF LESS THAN 2 PSI SYSTEM, PROVIDE A SIZING TABLE |
| | SELECTED FROM FBC FG 402.4 |
| | ***IF A 2PSI SYSTEM IS REQUIRED FOR DISTRIBUTION, THEN |
| | SPECIFY AND PROVIDE MP REGULATORS FOR FINAL |
| | CONNECTIONS. PROVIDE SIZING TABLE (FROM FBC FG 402.4) |
| | FOR REDUCED PRESSURE PIPING AND MAXIMUM DEVELOPED |
| | LENGTH OF REDUCED PRESSURE SYSTEM(S) FROM MP REGULATOR |
| | TO FINAL CONNECTIONS. SHOW LOCATIONS OF MP REGULATORS. |
| | |
| | 4. COMPLIED |
| | |
| | 5. COMPLIED |
| | |
| | 6. COMPLIED |
| | |
| | 7. COMPLIED |
| | |
| | 8. SECOND REQUEST:P-1/TANKLESS GAS WATER HEATER DETAIL |
| | INDICATES A CONCENTRIC VENT WITH SINGLE POINT |
| | CONNECTION FOR SINGLE HEATER. SCHEDULED NAVIEN NPE-240A |
| | AND P-1/HIGH TEMP DOMESTIC WATER HEATER DETAIL REQUIRES |
| | DEDICATED COMBUSTION AIR INLET AND EXHAUST OUTLET. |
| | REFER TO NAVIEN COMMON VENT SYSTEM INSTALLATION MANUAL. |
| | UPDATED DETAIL SHOWS A CONCENTRIC VENT MANIFOLD WITH |
| | SINGLE POINT CONNECTION FOR EACH OF THE THREE WATER |
| | HEATERS. |
| | NAVIEN COMMON VENT SYSTEM INSTALLATION MANUAL FOR |
| | SCHEDULED WATER HEATERS REQUIRES A DEDICATED INTAKE |
| | MANIFOLD AND A DEDICATED EXHAUST MANIFOLD. PER FBC FG |
| | 503.4, PROVIDE VENT SYSTEM IN ACCORDANCE WITH |
| | MANUFACTURER DIRECTIONS. |
| | |
| | PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE THE |
| | FOLLOWING: |
| | ***A) A DETAIL THAT PROPERLY ADDRESSES THE VENTING OF |
| | THE THREE UNITS. |
| | ***B) SIZE(S) AND MATERIAL SPECIFICATION FOR VENTS. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | |