Plan Review Notes
Plan Review Notes For Permit 22080183
Permit Number 22080183
Review Stop P
Sequence Number 1
Notes
Date Text
2022-09-07 17:05:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080183 4075 N HAVERHILL RD
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. P-2: CONFIRM LOCATION OF EXISTING BACKFLOW PREVENTER
 ON THE PLAN. IF A NEW BACKFLOW PREVENTER IS REQUIRED, A
 SEPARATE PERMIT IS REQUIRED AND IS REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS
 REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN
 PERMIT IS ALSO REQUIRED.
 ***PROVIDE DETAIL AND SCHEDULE FOR NEW BACKFLOW
 PREVENTER IF APPLICABLE.
  
 2. A SEPARATE PERMIT FOR THE SOLIDS INTERCEPTOR IS
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. A
 SEPARATE PERMIT IS REQUIRED HOWEVER A REVIEW OF THE
 SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED.
  
 3. PER WPB FBC 107.2.1, PLEASE PROVIDE THE
 MANUFACTURER'S INSTALLATION MANUAL FOR THE SCHEDULED
 SOLIDS INTERCEPTOR
  
 4. THE BUILDING DRAIN/SEWER PIPING TO THE INTERCEPTOR
 IS 6 INCH. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE
 P-1/SOLIDS INTERCEPTOR SPECIFICATION OPTION 6P FOR 6
 INCH INLET/OUTLET
  
 5. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE
 P-1/SOLIDS INTERCEPTOR SPECIFICATION THE FILTER OPTION
 TO BE INCORPORATED.
  
 6. P-2/KEYNOTE AND P-3/KEYNOTE 2 INDICATE SOLIDS
 INTERCEPTOR EFFLUENT SHALL CONNECT TO EXISTING 4 INCH
 SANITARY; INFLUENT SIZE IS 6 INCH. PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
  
 7. P-2 AND P-3 SHOWS A P-TRAP AHEAD OF THE SOLIDS
 INTERCEPTOR. PER FBC PL 901.2.1, A VENT IS REQUIRED
 DOWNSTREAM OF THE TRAP.
  
 8. THE VENT FOR THE 6 INCH COMBINATION WASTE AND VENT
 SYSTEM FOR THE CLOTHES WASHERS IS NOTED ON P-2/KEY NOTE
 1 AND P-3/KEY NOTE 1 AS A 3 INCH VENT THROUGH THE ROOF.
 P-3 SANITARY RISER DIAGRAM INDICATES A 2 INCH VENT
 CONNECTING TO 3 INCH VTR BY MEANS OF BRANCH VENT. PER
 FBC 906.2, THE VENT SHALL BE 3 INCH. PLEASE CLARIFY AND
 RECONCILE.
  
 9. SOLIDS INTERCEPTOR: PER WPB FBC 107.2.1, PROVIDE AN
 ENLARGED PIPING DIAGRAM SHOWING
 ***A) THE LOCATIONS OF CLEANOUTS AND VENTS AS REQUIRED
 BY THE MANUFACTURER AND FBC PL 1003.9.
 ***B) SIZE OF INFLUENT AND EFFLUENT PIPING
  
 10. SOLIDS INTERCEPTOR: PER WPB FBC 107.2.1, PROVIDE A
 SITE SPECIFIC, DIMENSIONED INSTALLATION DIAGRAM
 (ELEVATION) SHOWING THE BURIAL DEPTH AND INLET AND
 OUTLET LOCATIONS, CLEAN OUTS AND SIZES. INCLUDE SURFACE
 CONDITIONS (I.E. WALKWAY, TRAFFIC AREA, GRASSY AREA).
 COMPLY WITH MANUFACTURER'S INSTALLATION MANUAL. FBC PL
 301.7, 303.2.
  
 11. SOLIDS INTERCEPTOR: THE PLANS ARE UNCLEAR AS TO
 WHETHER THE UNIT IS IN AN AREA SUBJECT TO
 AUTOMOTIVE/HEAVY TRAFFIC. PER WPB FBC 107.2.1, CLARIFY.
 PER FBC PL 305.7 & 1003.10, PLEASE INDICATE ON THE
 P-1/SOLIDS INTERCEPTOR SPECIFICATION OPTION C24-HP FOR
 H20 LIDS IF APPLICABLE.
  
 12. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL
 FOR THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***WATER HEATERS
 ***CLOTHES WASHERS
 ***SOLIDS INTERCEPTOR
 ***HEAVY DUTY TRAFFIC LIDS
 ALL SUBMITTALS SHALL BE APPROVED AND STAMPED BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. DEFERRED
 SUBMITTALS SHALL BE LISTED ON THE PLANS. SUBMITTALS
 SHALL BE ON SITE PRIOR TO FIRST INSPECTION. PROCEED AT
 YOUR OWN RISK.
  
 13. A-1/ROOM FINISH SCHEDULE FOR BATHROOM WALLS: PER
 FBC 1210.2.2, FBC PL 310.3, WALLS WITHIN 2 FEET OF
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT NOT LESS THAN 4 FEET ABOVE THE
 FLOOR. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL BE
 "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 14. A-1/ROOM FINISH SCHEDULE FOR JANITORS ROOM: AMEND
 NOTE TO STATE *FRP TO 4 FEET MINIMUM AFF. FBC 1210.2.2,
 FBC PL 310.3
  
 15. P-1/PLUMBING NOTE 15: PER WPB FBC 107.2.1 AND FBC
 PL 604.9, REPLACE THE WORDS "APPROVED AIR CHAMBERS"
 WITH THE WORDS "WATER HAMMER ARRESTORS CONFORMING TO
 ASSE 1010"
  
 16. P-3: PER WPB FBC 107.2.1, PROVIDE WATER PIPE SIZES
 FOR CLOTHES WASHER BATTERY WATER PIPING.
  
 17. 18. P-3: PER WPB FBC 107.2.1, PROVIDE SIZE(S) FOR
 CLOTHES WASHER BATTERY SANITARY PIPING.
  
 19. P-3: PER WPB FBC 107.2.1, IDENTIFY THE FLOOR SINKS
 ON THE PLAN, PROVIDE SIZE.
  
 20. PER FBC EC C404.5.1 AND TABLE C404.5.1, THE 1/2
 -INCH HOT WATER PIPE TO THE LAVATORIES SHALL NOT EXCEED
 2 FEET FROM THE HOT WATER SOURCE.
  
 21. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 22. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 23. PROVIDE ENERGY EFFICIENCY FOR WATER HEATERS; COMPLY
 WITH FBC EC TABLE C404.2
  
 24. A THERMOSTATIC MIXING VALVE IS SHOWN ON P-1/HIGH
 TEMP DOMESTIC WATER HEATER DETAIL BUT NOT ON THE WATER
 DISTRIBUTION RISER AND PLAN VIEWS. PER WPB FBC 107.2.1,
 PLEASE CLARIFY AND RECONCILE.
  
 25. P-1/HIGH TEMP DOMESTIC WATER HEATER DETAIL: PER WPB
 FBC 107.2.1, PROVIDE A SCHEDULE AND SPECIFICATION FOR
 THE TMV.
  
 26. P-1/TANKLESS GAS WATER HEATER DETAIL: PER WPB FBC
 107.2.1, PROVIDE MEANS AND POINT OF TERMINATION FOR
 CONDENSATE DRAIN.
  
 27. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT."
  
 28. M-1/MECHANICAL PLAN NOTE H CALLS FOR A/C CONDENSATE
 TO NEAREST ROOF DRAIN OR INDIRECT WASTE. PER WPB CODE
 OF ORDINANCE CHAPTER 90, ARTICLE 3, SECTION 90-12B5,
 A/C CONDENSATE (INTERPRET THIS AS ANY CONDENSATION FROM
 EVAPORATOR COILS) SHALL NOT DISCHARGE TO THE CITY
 UTILITIES SANITARY SEWAGE INFRASTRUCTURE WITHOUT
 PERMISSION FROM THE UTILITIES DEPARTMENT. YOU MAY
 CONTACT MR. RICK ROSSANO IN ENGINEERING AT 561-494-1098
 FOR ADDITIONAL INFORMATION. MOVING FORWARD, REMOVE
 INDIRECT WASTE FROM THE NOTE. FBC PL 314.2.1.
  
 29. PER WPB FBC 107.2.1, PROVIDE RECIRCULATING PUMP
 SCHEDULE & DETAIL. INTEGRATE WITH P-1/HIGH TEMP
 DOMESTIC WATER HEATER DETAIL.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  