| 2022-09-07 17:05:39 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22080183 4075 N HAVERHILL RD |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. P-2: CONFIRM LOCATION OF EXISTING BACKFLOW PREVENTER |
| | ON THE PLAN. IF A NEW BACKFLOW PREVENTER IS REQUIRED, A |
| | SEPARATE PERMIT IS REQUIRED AND IS REQUIRED TO BE |
| | SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS |
| | REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN |
| | PERMIT IS ALSO REQUIRED. |
| | ***PROVIDE DETAIL AND SCHEDULE FOR NEW BACKFLOW |
| | PREVENTER IF APPLICABLE. |
| | |
| | 2. A SEPARATE PERMIT FOR THE SOLIDS INTERCEPTOR IS |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. A |
| | SEPARATE PERMIT IS REQUIRED HOWEVER A REVIEW OF THE |
| | SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED. |
| | |
| | 3. PER WPB FBC 107.2.1, PLEASE PROVIDE THE |
| | MANUFACTURER'S INSTALLATION MANUAL FOR THE SCHEDULED |
| | SOLIDS INTERCEPTOR |
| | |
| | 4. THE BUILDING DRAIN/SEWER PIPING TO THE INTERCEPTOR |
| | IS 6 INCH. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE |
| | P-1/SOLIDS INTERCEPTOR SPECIFICATION OPTION 6P FOR 6 |
| | INCH INLET/OUTLET |
| | |
| | 5. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE |
| | P-1/SOLIDS INTERCEPTOR SPECIFICATION THE FILTER OPTION |
| | TO BE INCORPORATED. |
| | |
| | 6. P-2/KEYNOTE AND P-3/KEYNOTE 2 INDICATE SOLIDS |
| | INTERCEPTOR EFFLUENT SHALL CONNECT TO EXISTING 4 INCH |
| | SANITARY; INFLUENT SIZE IS 6 INCH. PER WPB FBC 107.2.1, |
| | PLEASE CLARIFY. |
| | |
| | 7. P-2 AND P-3 SHOWS A P-TRAP AHEAD OF THE SOLIDS |
| | INTERCEPTOR. PER FBC PL 901.2.1, A VENT IS REQUIRED |
| | DOWNSTREAM OF THE TRAP. |
| | |
| | 8. THE VENT FOR THE 6 INCH COMBINATION WASTE AND VENT |
| | SYSTEM FOR THE CLOTHES WASHERS IS NOTED ON P-2/KEY NOTE |
| | 1 AND P-3/KEY NOTE 1 AS A 3 INCH VENT THROUGH THE ROOF. |
| | P-3 SANITARY RISER DIAGRAM INDICATES A 2 INCH VENT |
| | CONNECTING TO 3 INCH VTR BY MEANS OF BRANCH VENT. PER |
| | FBC 906.2, THE VENT SHALL BE 3 INCH. PLEASE CLARIFY AND |
| | RECONCILE. |
| | |
| | 9. SOLIDS INTERCEPTOR: PER WPB FBC 107.2.1, PROVIDE AN |
| | ENLARGED PIPING DIAGRAM SHOWING |
| | ***A) THE LOCATIONS OF CLEANOUTS AND VENTS AS REQUIRED |
| | BY THE MANUFACTURER AND FBC PL 1003.9. |
| | ***B) SIZE OF INFLUENT AND EFFLUENT PIPING |
| | |
| | 10. SOLIDS INTERCEPTOR: PER WPB FBC 107.2.1, PROVIDE A |
| | SITE SPECIFIC, DIMENSIONED INSTALLATION DIAGRAM |
| | (ELEVATION) SHOWING THE BURIAL DEPTH AND INLET AND |
| | OUTLET LOCATIONS, CLEAN OUTS AND SIZES. INCLUDE SURFACE |
| | CONDITIONS (I.E. WALKWAY, TRAFFIC AREA, GRASSY AREA). |
| | COMPLY WITH MANUFACTURER'S INSTALLATION MANUAL. FBC PL |
| | 301.7, 303.2. |
| | |
| | 11. SOLIDS INTERCEPTOR: THE PLANS ARE UNCLEAR AS TO |
| | WHETHER THE UNIT IS IN AN AREA SUBJECT TO |
| | AUTOMOTIVE/HEAVY TRAFFIC. PER WPB FBC 107.2.1, CLARIFY. |
| | PER FBC PL 305.7 & 1003.10, PLEASE INDICATE ON THE |
| | P-1/SOLIDS INTERCEPTOR SPECIFICATION OPTION C24-HP FOR |
| | H20 LIDS IF APPLICABLE. |
| | |
| | 12. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL |
| | FOR THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING: |
| | ***WATER HEATERS |
| | ***CLOTHES WASHERS |
| | ***SOLIDS INTERCEPTOR |
| | ***HEAVY DUTY TRAFFIC LIDS |
| | ALL SUBMITTALS SHALL BE APPROVED AND STAMPED BY THE |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC |
| | 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN |
| | ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. DEFERRED |
| | SUBMITTALS SHALL BE LISTED ON THE PLANS. SUBMITTALS |
| | SHALL BE ON SITE PRIOR TO FIRST INSPECTION. PROCEED AT |
| | YOUR OWN RISK. |
| | |
| | 13. A-1/ROOM FINISH SCHEDULE FOR BATHROOM WALLS: PER |
| | FBC 1210.2.2, FBC PL 310.3, WALLS WITHIN 2 FEET OF |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT |
| | SURFACE TO A HEIGHT NOT LESS THAN 4 FEET ABOVE THE |
| | FLOOR. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL BE |
| | "HARD." THE INTENT OF THIS SECTION IS THAT THE |
| | SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS |
| | EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME |
| | ABSORBENT AND THUS, NOT READILY CLEANABLE AND |
| | SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| | HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF |
| | SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS |
| | APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED |
| | PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED |
| | PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL. |
| | |
| | 14. A-1/ROOM FINISH SCHEDULE FOR JANITORS ROOM: AMEND |
| | NOTE TO STATE *FRP TO 4 FEET MINIMUM AFF. FBC 1210.2.2, |
| | FBC PL 310.3 |
| | |
| | 15. P-1/PLUMBING NOTE 15: PER WPB FBC 107.2.1 AND FBC |
| | PL 604.9, REPLACE THE WORDS "APPROVED AIR CHAMBERS" |
| | WITH THE WORDS "WATER HAMMER ARRESTORS CONFORMING TO |
| | ASSE 1010" |
| | |
| | 16. P-3: PER WPB FBC 107.2.1, PROVIDE WATER PIPE SIZES |
| | FOR CLOTHES WASHER BATTERY WATER PIPING. |
| | |
| | 17. 18. P-3: PER WPB FBC 107.2.1, PROVIDE SIZE(S) FOR |
| | CLOTHES WASHER BATTERY SANITARY PIPING. |
| | |
| | 19. P-3: PER WPB FBC 107.2.1, IDENTIFY THE FLOOR SINKS |
| | ON THE PLAN, PROVIDE SIZE. |
| | |
| | 20. PER FBC EC C404.5.1 AND TABLE C404.5.1, THE 1/2 |
| | -INCH HOT WATER PIPE TO THE LAVATORIES SHALL NOT EXCEED |
| | 2 FEET FROM THE HOT WATER SOURCE. |
| | |
| | 21. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| | BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| | 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| | STATING THE SAME. |
| | |
| | 22. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| | WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 23. PROVIDE ENERGY EFFICIENCY FOR WATER HEATERS; COMPLY |
| | WITH FBC EC TABLE C404.2 |
| | |
| | 24. A THERMOSTATIC MIXING VALVE IS SHOWN ON P-1/HIGH |
| | TEMP DOMESTIC WATER HEATER DETAIL BUT NOT ON THE WATER |
| | DISTRIBUTION RISER AND PLAN VIEWS. PER WPB FBC 107.2.1, |
| | PLEASE CLARIFY AND RECONCILE. |
| | |
| | 25. P-1/HIGH TEMP DOMESTIC WATER HEATER DETAIL: PER WPB |
| | FBC 107.2.1, PROVIDE A SCHEDULE AND SPECIFICATION FOR |
| | THE TMV. |
| | |
| | 26. P-1/TANKLESS GAS WATER HEATER DETAIL: PER WPB FBC |
| | 107.2.1, PROVIDE MEANS AND POINT OF TERMINATION FOR |
| | CONDENSATE DRAIN. |
| | |
| | 27. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL |
| | 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING |
| | LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF |
| | 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE |
| | A MINIMUM SLOPE OF 1/8 INCH PER FOOT." |
| | |
| | 28. M-1/MECHANICAL PLAN NOTE H CALLS FOR A/C CONDENSATE |
| | TO NEAREST ROOF DRAIN OR INDIRECT WASTE. PER WPB CODE |
| | OF ORDINANCE CHAPTER 90, ARTICLE 3, SECTION 90-12B5, |
| | A/C CONDENSATE (INTERPRET THIS AS ANY CONDENSATION FROM |
| | EVAPORATOR COILS) SHALL NOT DISCHARGE TO THE CITY |
| | UTILITIES SANITARY SEWAGE INFRASTRUCTURE WITHOUT |
| | PERMISSION FROM THE UTILITIES DEPARTMENT. YOU MAY |
| | CONTACT MR. RICK ROSSANO IN ENGINEERING AT 561-494-1098 |
| | FOR ADDITIONAL INFORMATION. MOVING FORWARD, REMOVE |
| | INDIRECT WASTE FROM THE NOTE. FBC PL 314.2.1. |
| | |
| | 29. PER WPB FBC 107.2.1, PROVIDE RECIRCULATING PUMP |
| | SCHEDULE & DETAIL. INTEGRATE WITH P-1/HIGH TEMP |
| | DOMESTIC WATER HEATER DETAIL. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | |