Plan Review Notes
Plan Review Notes For Permit 22080183
Permit Number 22080183
Review Stop M
Sequence Number 1
Notes
Date Text
2022-09-02 09:56:511ST REVIEW FMC
 PERMIT: 22080183
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS NEW LAUNDRY MAT.
  
 2) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS
 COMMERCIAL LAUNDRY INCLUDING ALL OF THE AREAS IN THIS
 TENANT SPACE. THE COIN OPERATED LAUNDRY WOULD NEED 711
 CFM?S OF OUTDOOR AIR. THE OFFICE AREA WOULD NEED 43
 CFM?S OF OUTDOOR AIR FOR A TOTAL OUTDOOR AIR REQUIRED
 OF 754 CFM?S. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 3) PROVIDE THE SPECS FOR THE DRYERS, INCLUDING THE
 EXHAUST DUCT INSTALLATION AND AN EXHAUST DUCT DRAWING
 FOR THESE DRYERS FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  