| 2022-09-07 17:15:46 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22080183 4075 N HAVERHILL RD |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR |
| | THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING: |
| | ***WATER HEATERS |
| | ***DRYERS (EACH MODEL UNIT) |
| | ***INLET/EXHAUST VENTS FOR WATER HEATERS |
| | ***REGULATORS |
| | ALL SUBMITTALS SHALL BE APPROVED AND STAMPED BY THE |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE PER WPB FBC |
| | 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN |
| | ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. DEFERRED |
| | SUBMITTALS SHALL BE LISTED ON THE PLANS. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER FBC FG |
| | 305.1. |
| | |
| | 2. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE ON THE GAS |
| | RISER DIAGRAM, ALL PIPE SIZES. |
| | |
| | 3. P-3/GAS RISER: REGULATOR AT METER REDUCES PRESSURE |
| | TO 7 INCHES WATER COLUMN; SIZING CALCULATIONS ARE BASED |
| | ON FBC FG TABLE 402.4(5) 2 PSI/1PD/6SG. PER WPB FBC |
| | 107.2.1, PLEASE CLARIFY AND RECONCILE. |
| | IF A 2PSI SYSTEM IS REQUIRED FOR DISTRIBUTION, THEN |
| | SPECIFY AND PROVIDE MP REGULATORS AT APPLIANCES. |
| | PROVIDE SIZING TABLE (FROM FBC FG 402.4) FOR REDUCED |
| | PRESSURE PIPING AND MAXIMUM DEVELOPED LENGTH OF REDUCED |
| | PRESSURE SYSTEM(S). PROVIDE DETAIL FOR MP REGULATOR |
| | CONNECTION TO APPLIANCE. COMPLY WITH FBC FG 409.4 AND |
| | 410.2. |
| | |
| | 4. PER WPB FBC 107.2.1, 107.2.1.2 AND 107.3.5.1.5, |
| | PROVIDE ON THE GAS RISER DIAGRAM, ITEM NUMBER AT EACH |
| | DRYER POC TO MATCH GAS SCHEDULE. |
| | |
| | 5. P-3/GAS SCHEDULE: PER WPB FBC 107.2.1, 107.3.5.1.5, |
| | PROVIDE BTU RATING PER UNIT FOR EACH DRYER MODEL AND |
| | FOR THE WATER HEATER. |
| | |
| | 6. P-3/GAS SCHEDULE INDICATES QUANTITY OF ONE (1) EACH |
| | WATER HEATER; P-1/HIGH TEMP DOMESTIC WATER HEATER |
| | DETAIL, P-2 PLAN AND P-3 RISER DIAGRAM INDICATE THREE |
| | (3) EACH. PER WPB FBC 107.2.1, PLEASE CLARIFY AND |
| | RECONCILE. |
| | |
| | 7. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE COMBUSTION |
| | AIR CALCULATIONS FOR THE DRYERS PER FBC FG 304.1. |
| | |
| | 8. P-1/TANKLESS GAS WATER HEATER DETAIL INDICATES A |
| | CONCENTRIC VENT WITH SINGLE POINT CONNECTION FOR SINGLE |
| | HEATER. SCHEDULED NAVIEN NPE-240A AND P-1/HIGH TEMP |
| | DOMESTIC WATER HEATER DETAIL REQUIRES DEDICATED |
| | COMBUSTION AIR INLET AND EXHAUST OUTLET. REFER TO |
| | NAVIEN COMMON VENT SYSTEM INSTALLATION MANUAL. |
| | PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE THE |
| | FOLLOWING: |
| | ***A) A DETAIL THAT PROPERLY ADDRESSES THE VENTING OF |
| | THE THREE UNITS. |
| | ***B) SIZE(S) AND MATERIAL SPECIFICATION FOR VENTS. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | |