Plan Review Notes
Plan Review Notes For Permit 22080183
Permit Number 22080183
Review Stop G
Sequence Number 1
Notes
Date Text
2022-09-07 17:15:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080183 4075 N HAVERHILL RD
  
 GAS COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***WATER HEATERS
 ***DRYERS (EACH MODEL UNIT)
 ***INLET/EXHAUST VENTS FOR WATER HEATERS
 ***REGULATORS
 ALL SUBMITTALS SHALL BE APPROVED AND STAMPED BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE PER WPB FBC
 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. DEFERRED
 SUBMITTALS SHALL BE LISTED ON THE PLANS. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER FBC FG
 305.1.
  
 2. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE ON THE GAS
 RISER DIAGRAM, ALL PIPE SIZES.
  
 3. P-3/GAS RISER: REGULATOR AT METER REDUCES PRESSURE
 TO 7 INCHES WATER COLUMN; SIZING CALCULATIONS ARE BASED
 ON FBC FG TABLE 402.4(5) 2 PSI/1PD/6SG. PER WPB FBC
 107.2.1, PLEASE CLARIFY AND RECONCILE.
 IF A 2PSI SYSTEM IS REQUIRED FOR DISTRIBUTION, THEN
 SPECIFY AND PROVIDE MP REGULATORS AT APPLIANCES.
 PROVIDE SIZING TABLE (FROM FBC FG 402.4) FOR REDUCED
 PRESSURE PIPING AND MAXIMUM DEVELOPED LENGTH OF REDUCED
 PRESSURE SYSTEM(S). PROVIDE DETAIL FOR MP REGULATOR
 CONNECTION TO APPLIANCE. COMPLY WITH FBC FG 409.4 AND
 410.2.
  
 4. PER WPB FBC 107.2.1, 107.2.1.2 AND 107.3.5.1.5,
 PROVIDE ON THE GAS RISER DIAGRAM, ITEM NUMBER AT EACH
 DRYER POC TO MATCH GAS SCHEDULE.
  
 5. P-3/GAS SCHEDULE: PER WPB FBC 107.2.1, 107.3.5.1.5,
 PROVIDE BTU RATING PER UNIT FOR EACH DRYER MODEL AND
 FOR THE WATER HEATER.
  
 6. P-3/GAS SCHEDULE INDICATES QUANTITY OF ONE (1) EACH
 WATER HEATER; P-1/HIGH TEMP DOMESTIC WATER HEATER
 DETAIL, P-2 PLAN AND P-3 RISER DIAGRAM INDICATE THREE
 (3) EACH. PER WPB FBC 107.2.1, PLEASE CLARIFY AND
 RECONCILE.
  
 7. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE COMBUSTION
 AIR CALCULATIONS FOR THE DRYERS PER FBC FG 304.1.
  
 8. P-1/TANKLESS GAS WATER HEATER DETAIL INDICATES A
 CONCENTRIC VENT WITH SINGLE POINT CONNECTION FOR SINGLE
 HEATER. SCHEDULED NAVIEN NPE-240A AND P-1/HIGH TEMP
 DOMESTIC WATER HEATER DETAIL REQUIRES DEDICATED
 COMBUSTION AIR INLET AND EXHAUST OUTLET. REFER TO
 NAVIEN COMMON VENT SYSTEM INSTALLATION MANUAL.
 PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE THE
 FOLLOWING:
 ***A) A DETAIL THAT PROPERLY ADDRESSES THE VENTING OF
 THE THREE UNITS.
 ***B) SIZE(S) AND MATERIAL SPECIFICATION FOR VENTS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  