2022-09-22 01:55:00FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) CIRCUITS 13,15,17,19,21,23 TO BE GFCI PROTECTED PER
 422.5 , 210.8(B)
  
 APPLIANCES IDENTIFIED IN 422.5(A)(1) THROUGH (5) RATED
 250 VOLTS OR LESS AND 60 AMPERES OR LESS, SINGLE- OR
 3-???PHASE, SHALL BE PROVIDED WITH GFCI PROTECTION FOR
 PERSONNEL. MULTIPLE GFCI PROTECTIVE DEVICES SHALL BE
 PERMITTED BUT SHALL NOT BE REQUIRED.
 (1) AUTOMOTIVE VACUUM MACHINES PROVIDED FOR PUBLIC USE
  
 (2) DRINKING WATER COOLERS
  
 (3) HIGH-PRESSURE SPRAY WASHING MACHINES ???
 CORD-AND-PLUG-CONNECTED
  
 (4) TIRE INFLATION MACHINES PROVIDED FOR PUBLIC USE
  
 (5) VENDING MACHINE