| Plan Review Notes For Permit 22080180 |
| Permit Number |
22080180 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-26 17:28:10 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SHEET #3 HAS A SECTION THROUGH THE PORCH THAT SHOWS | | | 2X8 RAFTERS THAT HAVE BEEN RIPPED TO ACHIEVE A 1" TO | | | 12" ROOF SLOPE. THIS NEEDS TO BE CORRECTED. THE 2X8S | | | ARE TYPICALLY 7.5" AND IF THEY ARE CUT TO MAKE THE 1:12 | | | SLOPE THERE WILL BE NO RAFTER LEFT AT 7.5 FEET AND THE | | | PORCH IS OVER 9 FT. FBC 107.2.1. | | | | | | 2) THIS IS A LEVEL II ALTERATION. FBC EXISTING BUILDING | | | CHAPTER 8 | | | | | | 3) THE CONSTRUCTION IS VB NOT III. UNLESS YOU WANT TO | | | MEET THE REQUIREMENTS FOR TYPE III CONSTRUCTION. FBC | | | CHAPTER 6 | | | | | | 4) THE PROFILE VIEW ON SHEET #3 APPEARS THAT A RAKE | | | BEAM IS REQUIRED. CLARIFY AND PROVIDE DETAILS. FBC | | | 107.2.1 | | | | | | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|