| 2022-11-02 16:05:08 | ROOFING: |
| | |
| | 1-PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | |
| | ORIGINAL COMMENT: |
| | A)ROOF TILE NOA SUBMITTED: CLEARLY MARK ROOF TILE |
| | FASTENING TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R3012.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | USING THE FRSA MANUAL AS A REFERENCE, THE PROPOSED |
| | FASTENING METHOD DOESN'T WORK. THE ATTACHMENT |
| | RESISTANCE MOMENT SHOWN ON TABLE 4 OF NOA SUBMITTED FOR |
| | 2-10D RING SHANK NAILS DOESN'T MEET THE ATTACHMENT |
| | RESISTANCE MOMENT OF TABLE 2HD OF THE FRSA MANUAL. |
| | REVISE FASTENING METHOD THAT MEET THE OR PROVIDE SIGNED |
| | AND SEALED CALCULATIONS FOR ATTACHMENT RESISTANCE |
| | MOMENT SHOWING THAT PROPOSED FASTENING METHOD WORKS. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | NOTE: I USED 3-1/2 ROOF PITCH AND THE 30FT MEAN ROOF |
| | HEIGHT WHEN USING THE FRSA MANUAL. |
| | |
| | B) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: COORDINATE WITH PRODUCT APPROVAL COMMENTS ABOVE. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | AUDIT PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |