| 2022-11-02 16:04:35 | RESIDENTIAL(R3) THIRD BUILDING AUDIT. |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22080160 |
| | 263 BARCELONA RD |
| | |
| | 1- OK. |
| | 2- OK. |
| | |
| | 3- SHEET A-5: |
| | A)OK. |
| | B)OK. |
| | |
| | ORIGINAL COMMENT : |
| | C)ROOF SHEATHING NAILING SPECIFICATIONS TO COMPLY WITH |
| | NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. REVISE TYPE, |
| | SIZE AND SPACING. NOTE: NEED TO USE RING SHANK NAILS. |
| | ROOF SHEATHING NEEDS TO BE NAILED AT 4 INCHES O.C. IN |
| | THE FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND |
| | TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| | NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS |
| | SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR |
| | EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM |
| | REQUIREMENTS. |
| | |
| | RESPONSE: |
| | NAIL SPACING FOR ROOF SHEATHING TABLE WAS REVISED. THE |
| | WIND SPEED FOR THE CITY OF WEST PALM BEACH IS 170MPH |
| | NOT 140MPH AS CIRCLED ON THE REVISED TABLE. REVISE AS |
| | REQUIRED. |
| | NOTE: SEE TABLE R803.2.3.1 FBC-RESIDENTIAL AND REVISE |
| | SPACING AS SHOWN ON TABLE FOR 170MPH AND WOOD SPECIFIC |
| | GRAVITY (SG=.42)SELECTED BY THE ARCHITECT. |
| | |
| | |
| | D)NOTE: |
| | SHUTTERS FOR EXISTING WINDOWS UNDER A SEPARATE PERMIT. |
| | NOTE: THERE WILL BE A HOLD ON PERMIT FOR FINAL |
| | INSPECTION TO VERIFY SHUTTERS PERMIT. |
| | |
| | 4- OK. |
| | |
| | 5-PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | |
| | ORIGINAL COMMENT: |
| | A)WINDOW MULLIONS IF USED. COORDINATE WITH ITEM #1(A) |
| | ABOVE FOR BAY WINDOW. |
| | NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY PRESSURES. |
| | SEC. R301.2.1 FBC-RESIDENTIAL). |
| | |
| | RESPONSE: |
| | WINDOW MULLION PRODUCT APPROVAL FL14239-R5 UPLOADED TO |
| | PROJECTDOX ON 10/24/22 IS FOR A/C TIE DOWNS NOT FOR |
| | WINDOW MULLIONS. NEED TO UPLOAD CORRECT PRODUCT |
| | APPROVAL. |
| | |
| | B)OK. |
| | ORIGINAL COMMENT: |
| | B)ROOF TILE NOA SUBMITTED: CLEARLY MARK ROOF TILE |
| | FASTENING TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R3012.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | USING THE FRSA MANUAL AS A REFERENCE, THE PROPOSED |
| | FASTENING METHOD DOESN'T WORK. THE ATTACHMENT |
| | RESISTANCE MOMENT SHOWN ON TABLE 4 OF NOA SUBMITTED FOR |
| | 2-10D RING SHANK NAILS DOESN'T MEET THE ATTACHMENT |
| | RESISTANCE MOMENT OF TABLE 2HD OF THE FRSA MANUAL. |
| | REVISE FASTENING METHOD THAT MEET THE OR PROVIDE SIGNED |
| | AND SEALED CALCULATIONS FOR ATTACHMENT RESISTANCE |
| | MOMENT SHOWING THAT PROPOSED FASTENING METHOD WORKS. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | NOTE: I USED 3-1/2 ROOF PITCH AND THE 30FT MEAN ROOF |
| | HEIGHT WHEN USING THE FRSA MANUAL. |
| | |
| | C)OK. |
| | |
| | ORIGINAL COMMENT: |
| | D)INSTALLATION INSTRUCTIONS SUBMITTED FOR FLORIDA |
| | PRODUCT APPROVAL FL14239-R5 FOR A/C UNIT ANCHORS DON'T |
| | CORRESPOND TO THIS PRODUCT APPROVAL. INSTALLATION |
| | INSTRUCTIONS SUBMITTED ARE FOR 2017 CODE VERSION. NEED |
| | TO SUBMIT CORRECT INSTALLATION INSTRUCTIONS. |
| | |
| | RESPONSE: |
| | INSTALLATION INSTRUCTIONS STILL DON'T MATCH. FLORIDA |
| | PRODUCT APPROVAL FL14239-R5 IS FOR BMP INTERNATIONAL |
| | INC. DRAWINGS SUBMITTED ARE FOR MIAMI TECH INC. PROVIDE |
| | MATCHING INFORMATION. |
| | |
| | ORIGINAL COMMENT: |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | COORDINATE WITH PRODUCT APPROVAL COMMENTS ABOVE. |
| | |
| | NEW COMMENT BASED ON REVISED DRAWING T-1: |
| | 7- DESIGN PARAMETERS INFORMATION ON SHEET T-1 WAS |
| | REVISED. THE BUILDING EXPOSURE WAS CHANGED FROM |
| | EXPOSURE "D" TO EXPOSURE "C". ARCHITECT TO CLARIFY WHY |
| | THE BUILDING EXPOSURE WAS REVISED IF IT WAS OK. |
| | EXPOSURE "D" IS THE CORRECT EXPOSURE. |
| | SEC. R301.2.1.4 FBC-RESIDENTIAL. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | AUDIT PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |