| 2022-10-14 18:30:46 | RESIDENTIAL(R3) SECOND BUILDING AUDIT. |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22080160 |
| | 263 BARCELONA RD |
| | |
| | 1- OK. |
| | 2- OK. |
| | |
| | 3- SHEET A-5: |
| | ORIGINAL COMMENT: |
| | A)ROOF DIAGRAMS DON'T MATCH ROOF DIAGRAMS OF CURRENT |
| | CODE FIGURE R301.2(7)FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REVISED ROOF DIAGRAMS DON'T MATCH FIGURE |
| | R301.2(7)FBC-RESIDENTIAL. REVISE ROOF ZONES AS REQUIRED |
| | TO MATCH. |
| | NOTE: REVISE ROOF ZONES ON THE "NAIL SPACING FOR ROOF |
| | SHEATHING" TABLE ACCORDINGLY. |
| | |
| | B)OK. |
| | |
| | ORIGINAL COMMENT: |
| | C)ROOF SHEATHING NAILING SPECIFICATIONS TO COMPLY WITH |
| | NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. REVISE TYPE, |
| | SIZE AND SPACING. NOTE: NEED TO USE RING SHANK NAILS. |
| | ROOF SHEATHING NEEDS TO BE NAILED AT 4 INCHES O.C. IN |
| | THE FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND |
| | TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| | NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS |
| | SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR |
| | EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM |
| | REQUIREMENTS. |
| | |
| | RESPONSE: |
| | ROOF SHEATHING THICKNESS OF 15/32" DOESN'T COMPLY WITH |
| | TABLE R803.2.2 FBC-RESIDENTIAL. ALSO, 8D RING SHANK |
| | NAILS ARE NOT 3" LONG. REVISE AS REQUIRED. |
| | |
| | ORIGINAL COMMENT: |
| | D)THERE IS NOT TABLE R301.2.1.2 IN 2020 |
| | FBC-RESIDENTIAL. THIS TABLE DOESN'T APPLY. REVISE AS |
| | REQUIRED. |
| | |
| | RESPONSE: |
| | WOOD STRUCTURAL PANELS INFORMATION NEEDS TO BE REVISED |
| | TO COMPLY WITH THE EXCEPTION OF SECTION R301.2.1.2 |
| | FBC-RESIDENTIAL. THE PANEL SPAN AND THE BUILDING MEAN |
| | ROOF HEIGHT DOESN'T MATCH THE INFORMATION REQUIRED BY |
| | THE EXCEPTION OF SECTION R301.2.1.2 FBC-RESIDENTIAL. |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE FOR EACH OPENING |
| | WHERE WOOD STRUCTURAL PANELS ARE GOING TO BE INSTALLED. |
| | SPECIFY PANEL SIZE AND ANCHOR TYPE AND SPACING. |
| | PROVIDE INFORMATION ON HOW THE PANELS NEED TO BE PRECUT |
| | AND INSTALLED. ALSO, NEED TO REVISE THE FASTENER TYPE |
| | SIZE. 2 INCH WOOD SCREWS DON'T PROVIDE 2 INCHES |
| | PENETRATION INTO THE BUILDING FRAME AS REQUIRED ON NOTE |
| | "C". CLARIFY IF PANELS ARE INSTALLED PER SEC. |
| | R301.2.1.2 FBC-RESIDENTIAL OR PER THE ALTERNATIVE (B) |
| | SHOWN IN THIS SECTION. NOTE THAT SECTION R301.2.1.2 |
| | FBC-RESIDENTIAL REQUIRES FASTENERS TO BE ATTACHED TO |
| | THE FRAMING SURROUNDING THE OPENING. THE ALTERNATIVE |
| | (B) SPECIFIES FASTENERS ALONG THE EDGES OF THE OPPOSING |
| | LONG SIDES OF THE PANEL AND THE ANCHOR TYPE IS |
| | DIFFERENT THAN ONE SHOWN ON THE TABLE SUBMITTED. |
| | NOTE: PROVIDE COMPLETE REVISED INFORMATION NOW OR |
| | PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT. |
| | |
| | 4- OK. |
| | |
| | 5-PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | |
| | ORIGINAL COMMENT: |
| | A)WINDOW MULLIONS IF USED. COORDINATE WITH ITEM #1(A) |
| | ABOVE FOR BAY WINDOW. |
| | NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY PRESSURES. |
| | SEC. R301.2.1 FBC-RESIDENTIAL). |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | B)ROOF TILE NOA SUBMITTED: CLEARLY MARK ROOF TILE |
| | FASTENING TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R3012.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | C)ROOF TILE ADHESIVE IF SPECIFIED ON THE ROOF TILE NOA. |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | D)INSTALLATION INSTRUCTIONS SUBMITTED FOR FLORIDA |
| | PRODUCT APPROVAL FL14239-R5 FOR A/C UNIT ANCHORS DON'T |
| | CORRESPOND TO THIS PRODUCT APPROVAL. INSTALLATION |
| | INSTRUCTIONS SUBMITTED ARE FOR 2017 CODE VERSION. NEED |
| | TO SUBMIT CORRECT INSTALLATION INSTRUCTIONS. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | AUDIT PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |