2022-10-14 18:30:46RESIDENTIAL(R3) SECOND BUILDING AUDIT.
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22080160
 263 BARCELONA RD
  
 1- OK.
 2- OK.
  
 3- SHEET A-5:
 ORIGINAL COMMENT:
 A)ROOF DIAGRAMS DON'T MATCH ROOF DIAGRAMS OF CURRENT
 CODE FIGURE R301.2(7)FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISED ROOF DIAGRAMS DON'T MATCH FIGURE
 R301.2(7)FBC-RESIDENTIAL. REVISE ROOF ZONES AS REQUIRED
 TO MATCH.
 NOTE: REVISE ROOF ZONES ON THE "NAIL SPACING FOR ROOF
 SHEATHING" TABLE ACCORDINGLY.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C)ROOF SHEATHING NAILING SPECIFICATIONS TO COMPLY WITH
 NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. REVISE TYPE,
 SIZE AND SPACING. NOTE: NEED TO USE RING SHANK NAILS.
 ROOF SHEATHING NEEDS TO BE NAILED AT 4 INCHES O.C. IN
 THE FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND
 TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 RESPONSE:
 ROOF SHEATHING THICKNESS OF 15/32" DOESN'T COMPLY WITH
 TABLE R803.2.2 FBC-RESIDENTIAL. ALSO, 8D RING SHANK
 NAILS ARE NOT 3" LONG. REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 D)THERE IS NOT TABLE R301.2.1.2 IN 2020
 FBC-RESIDENTIAL. THIS TABLE DOESN'T APPLY. REVISE AS
 REQUIRED.
  
 RESPONSE:
 WOOD STRUCTURAL PANELS INFORMATION NEEDS TO BE REVISED
 TO COMPLY WITH THE EXCEPTION OF SECTION R301.2.1.2
 FBC-RESIDENTIAL. THE PANEL SPAN AND THE BUILDING MEAN
 ROOF HEIGHT DOESN'T MATCH THE INFORMATION REQUIRED BY
 THE EXCEPTION OF SECTION R301.2.1.2 FBC-RESIDENTIAL.
 PROVIDE COMPLETE INSTALLATION SCHEDULE FOR EACH OPENING
 WHERE WOOD STRUCTURAL PANELS ARE GOING TO BE INSTALLED.
 SPECIFY PANEL SIZE AND ANCHOR TYPE AND SPACING.
 PROVIDE INFORMATION ON HOW THE PANELS NEED TO BE PRECUT
 AND INSTALLED. ALSO, NEED TO REVISE THE FASTENER TYPE
 SIZE. 2 INCH WOOD SCREWS DON'T PROVIDE 2 INCHES
 PENETRATION INTO THE BUILDING FRAME AS REQUIRED ON NOTE
 "C". CLARIFY IF PANELS ARE INSTALLED PER SEC.
 R301.2.1.2 FBC-RESIDENTIAL OR PER THE ALTERNATIVE (B)
 SHOWN IN THIS SECTION. NOTE THAT SECTION R301.2.1.2
 FBC-RESIDENTIAL REQUIRES FASTENERS TO BE ATTACHED TO
 THE FRAMING SURROUNDING THE OPENING. THE ALTERNATIVE
 (B) SPECIFIES FASTENERS ALONG THE EDGES OF THE OPPOSING
 LONG SIDES OF THE PANEL AND THE ANCHOR TYPE IS
 DIFFERENT THAN ONE SHOWN ON THE TABLE SUBMITTED.
 NOTE: PROVIDE COMPLETE REVISED INFORMATION NOW OR
 PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT.
  
 4- OK.
  
 5-PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
  
 ORIGINAL COMMENT:
 A)WINDOW MULLIONS IF USED. COORDINATE WITH ITEM #1(A)
 ABOVE FOR BAY WINDOW.
 NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY PRESSURES.
 SEC. R301.2.1 FBC-RESIDENTIAL).
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B)ROOF TILE NOA SUBMITTED: CLEARLY MARK ROOF TILE
 FASTENING TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R3012.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 C)ROOF TILE ADHESIVE IF SPECIFIED ON THE ROOF TILE NOA.
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D)INSTALLATION INSTRUCTIONS SUBMITTED FOR FLORIDA
 PRODUCT APPROVAL FL14239-R5 FOR A/C UNIT ANCHORS DON'T
 CORRESPOND TO THIS PRODUCT APPROVAL. INSTALLATION
 INSTRUCTIONS SUBMITTED ARE FOR 2017 CODE VERSION. NEED
 TO SUBMIT CORRECT INSTALLATION INSTRUCTIONS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 AUDIT PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JULIO GOMEZ