| Date |
Text |
| 2022-08-29 09:59:06 | |
| | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22080160 |
| | 8/29/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLEASE NOTE THAT THE GAS |
| | WORK FOR THE PROPOSED PROJECT CAN BE UNDER A SEPARATE |
| | PERMIT BY CONTRACTOR REQUEST. PLEASE REVIEW THE |
| | COMMENTS BELOW AND CORRECT THE PLANS. |
| | |
| | 1) SHEET A-1: PLEASE CORRECT THE NOTE SPECIFYING AN |
| | ELECTRIC TANKLESS WATER HEATER. THE PLUMBING PLANS ARE |
| | SPECIFYING A GAS-FIRED TANKLESS WATER HEATER- SEC. |
| | 107.2.1 WPB. |
| | |
| | 2) P-2: CORRECT THE GAS RISER INDICATING A 35 MBH GAS |
| | GENERATOR. WPB BUILDING DEPT. RECORDS INDICATE A 281 |
| | MBH GENERATOR WAS INSTALLED UNDER PERMIT 16020522- SEC. |
| | G2413.1 FBC RES. TOTAL CORRECTED LOAD- 623.2 MBH |
| | (623,200 BTUH). |
| | |
| | 3) P-2: THE APPROVED GAS PLANS UNDER PERMIT-16020523 |
| | SHOWS THE GAS METER ATTACHED TO THE HOUSE. THE NEW |
| | PLANS INDICATE THE EXISTING METER LOCATION TO BE BY THE |
| | CARRIAGE HOUSE. PLEASE CLARIFY IF THE METER IS BEING |
| | RELOCATED UNDER THIS PERMIT, AND IF ANY PIPING IS BEING |
| | RUN UNDERGROUND FROM THE METER TO THE HOUSE- SEC. |
| | G2415.11 FBC RES. |
| | |
| | 4) P-2: PROVIDE SUPPORT DETAILS FOR SCHEDULE 40 STEEL |
| | PIPING RUN ABOVEGROUND AT GRADE LEVEL- SEC. G2415.9 FBC |
| | RES. |
| | |
| | 5) P-2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | RANGE- SEC. G2407.1 FBC RES. |
| | |
| | 6) P-1 & P-2: A SEPARATE PERMIT IS REQUIRED FOR |
| | RELOCATING THE GENERATOR HOWEVER IT APPEARS THAT THE |
| | NEW LOCATION CLOSE TO THE PANTRY WINDOW IS NOT IN |
| | COMPLIANCE WITH SEC. R303.5.1 FBC RES- 10 FT. CLEARANCE |
| | REQUIRED TO MECHANICAL AND GRAVITY AIR INTAKES INTO THE |
| | BUILDING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |