| Date |
Text |
| 2022-08-24 15:57:20 | RESIDENTIAL (R3) BUILDING AUDIT. |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22080160 |
| | 263 BARCELONA RD |
| | |
| | NOTE: |
| | LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| | SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | 1-SHEET A-1: |
| | A) NEW BAY WINDOW. MISSING FRAMING INFORMATION. PROVIDE |
| | COMPLETE FRAMING DETAILS AND SPECIFICATIONS. SPECIFY |
| | ALL STRUCTURAL FRAMING MEMBERS AND CONNECTORS AT EACH |
| | END. THERE IS NOT HEADER INFORMATION AT ENLARGED WALL |
| | OPENING. PROVIDE COMPLETE WALL SECTION FROM ROOF TO |
| | CANTILEVERED FLOOR. SPECIFY WINDOW MULLIONS, ROOF TO |
| | NEW BAY WALL CONNECTION, ROOF TO EXISTING WALL |
| | CONNECTION, ETC. SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | B)PROVIDE DETAILS AND SPECIFICATIONS FOR NEW AWNING OR |
| | SPECIFY BY OTHERS UNDER A SEPARATE PERMIT. SEC. |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 2- DOOR AND WINDOW SCHEDULES ON SHEET A-4: |
| | A) ARCHITECT TO JUSTIFY HOW THE EXISTING DOORS AND |
| | WINDOWS MEET THE DESIGN PRESSURES SPECIFIED ON THE |
| | SCHEDULES. ALSO, JUSTIFY WHY THE SCHEDULES STATE THAT |
| | EXISTING DOORS AND WINDOWS HAVE IMPACT GLASS. . |
| | SEC. 107.2.1.2 CITY AMENDMENTS. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. SEC. R301.2.2 FBC-RESIDENTIAL. |
| | |
| | B) ARCHITECT TO PROVIDE INSTALLATION SPECIFICATIONS FOR |
| | RELOCATED WINDOWS TO MEET THE SPECIFIED DESIGN |
| | PRESSURES. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. |
| | R301.2.1 FBC-RESIDENTIAL. SEC. R301.2.2 |
| | FBC-RESIDENTIAL. |
| | |
| | C)WINDOW 2P NEEDS TO COMPLY WITH GLAZING IN HAZARDOUS |
| | LOCATIONS SEC. R308.4.2 FBC-RESIDENTIAL. SHOW |
| | COMPLIANCE. |
| | NOTE: WINDOW 2M IS ALSO ADJACENT TO THE DOOR. THERE IS |
| | A NOTE ON SHEET A-2 STATING "CLOSE OFF WINDOW FROM |
| | INTERIOR (SPANDREL WINDOW). PROVIDE |
| | DETAIL/SPECIFICATIONS SHOWING HOW THE WINDOW IS CLOSED |
| | AND COMPLIES WITH THIS SECTION. |
| | |
| | 3- SHEET A-5: |
| | A)ROOF DIAGRAMS DON'T MATCH ROOF DIAGRAMS OF CURRENT |
| | CODE FIGURE R301.2(7)FBC-RESIDENTIAL. |
| | |
| | B)WIND SPEED SPECIFIED BELOW THE ROOF DIAGRAMS DON'T |
| | MATCH DESIGN CRITERIA SPECIFIED ON OTHER SHEETS. SEC. |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | C)ROOF SHEATHING NAILING SPECIFICATIONS TO COMPLY WITH |
| | NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. REVISE TYPE, |
| | SIZE AND SPACING. NOTE: NEED TO USE RING SHANK NAILS. |
| | ROOF SHEATHING NEEDS TO BE NAILED AT 4 INCHES O.C. IN |
| | THE FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND |
| | TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| | NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS |
| | SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR |
| | EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM |
| | REQUIREMENTS. |
| | |
| | D)THERE IS NOT TABLE R301.2.1.2 IN 2020 |
| | FBC-RESIDENTIAL. THIS TABLE DOESN'T APPLY. REVISE AS |
| | REQUIRED. |
| | |
| | 4- REVISE ENERGY CALCULATIONS: |
| | A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE |
| | AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700). |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B)REVISE THE ATTIC VENT RATIO ON PAGE 3. TYPICALLY, THE |
| | RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. |
| | OR ARCHITECT CERTIFYING THE ENERGY CALCULATIONS ON PAGE |
| | ONE TO PROVIDE COMPLETE DETAILS/SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE 1/300 RATIO AS REQUIRED BY THE |
| | EXCEPTION ON SEC. R806.2 FBC-RESIDENTIAL. |
| | |
| | C)DOORS INFORMATION ON PAGE 4 IS INCORRECT. THE FRONT |
| | DOOR IS NOT FACING NORTH. SOUTH AND WEST DOORS DON'T |
| | MATCH PLANS. THEY ARE SHOWN AS DOORS WITH GLAZING. |
| | NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE |
| | WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY |
| | CONSERVATION). |
| | |
| | D)WINDOWS INFORMATION ON PAGE 5 IS INCORRECT. REVISE |
| | WINDOWS INFORMATION TO MATCH PLANS AND PRODUCT |
| | APPROVALS. REVISE FRAME TYPE, WINDOW ORIENTATION, AREA, |
| | WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | 5-PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | A)WINDOW MULLIONS IF USED. COORDINATE WITH ITEM #1(A) |
| | ABOVE FOR BAY WINDOW. |
| | NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY PRESSURES. |
| | SEC. R301.2.1 FBC-RESIDENTIAL). |
| | |
| | B)ROOF TILE NOA SUBMITTED: CLEARLY MARK ROOF TILE |
| | FASTENING TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R3012.1 FBC-RESIDENTIAL. |
| | |
| | C)ROOF TILE ADHESIVE IF SPECIFIED ON THE ROOF TILE NOA. |
| | |
| | D)INSTALLATION INSTRUCTIONS SUBMITTED FOR FLORIDA |
| | PRODUCT APPROVAL FL14239-R5 FOR A/C UNIT ANCHORS DON'T |
| | CORRESPOND TO THIS PRODUCT APPROVAL. INSTALLATION |
| | INSTRUCTIONS SUBMITTED ARE FOR 2017 CODE VERSION. NEED |
| | TO SUBMIT CORRECT INSTALLATION INSTRUCTIONS. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |