Plan Review Notes
Plan Review Notes For Permit 22080113
Permit Number 22080113
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-09-02 12:22:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION PROVIDING FOR AN AREA OF
 REFUGE.
  
 FOR CLARIFICATION PURPOSES, THIS A AREA OF REFUGE FOR
 THIS OCCUPANCY IS NOT REQUIRED BY THE FIRE CODE.
  
 THE CITED LIFE SAFETY CODE ON SHEET TW 1.01 IS A
 PERMITTED CODE NOT A REQUIRED CODE, MEANING THAT IF AN
 AREA OF REFUGE IS REQUIRED IT SHALL BE PERMITTED TO BE
 INSTALLED PER THAT CODE.
  
 AN AREA OF REFUGE REQUIREMENT IS CONTAINED IN THE FBC
 UNDER ACCESSIBILITY, HOWEVER, THERE IS A EXCEPTION
 WHERE IT IS NOT REQUIRED IF THE BUILDING IS PROTECTED
 WWITH A FIRE SPRINKLER SYSTEM.
  
 PLEASE REVIEW AND ENSURE THAT YOU WANT THIS SYSTEM
 INSTALLED.
  
  
  
 2) PER THE REQUIREMENT OF INSTALLATION IN NFPA 101
  
 7.2.12.2.4* WHERE AN ELEVATOR PROVIDES ACCESS FROM AN
 AREA OF REFUGE
 TO A PUBLIC WAY THAT IS IN ACCORDANCE WITH 7.2.12.2.2,
 ALL OF THE FOLLOWING
 CRITERIA SHALL BE MET:
 (1) THE ELEVATOR SHALL BE APPROVED FOR FIRE FIGHTERS?
 EMERGENCY OPERATIONS AS PROVIDED IN ASME A17.1/CSA B44,
 SAFETY CODE FOR ELEVA TORS AND ESCALATORS.
 (2) THE POWER SUPPLY SHALL BE PROTECTED AGAINST
 INTERRUPTION FROM FIRE
 OCCURRING WITHIN THE BUILDING BUT OUTSIDE THE AREA OF
 REFUGE.
 (3) THE ELEVATOR SHALL BE LOCATED IN A SHAFT SYSTEM
 MEETING THE REQUIREMENTS FOR SMOKEPROOF ENCLOSURES IN
 ACCORDANCE WITH 7.2.3, UNLESS
 OTHERWISE PROVIDED IN 7.2.12.2.4.1 AND 7.2.12.2.4.2.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
2022-09-01 15:08:27 
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved