| 2022-08-12 11:49:52 | 2ND REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 22080081 |
| | 8/12/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS #1 & 2 FROM THE |
| | 1ST REVIEW STILL EXIST- PLEASE COMPLY. |
| | |
| | 1) THE SCOPE OF WORK FOR THE PERMIT APPEARS TO BE A |
| | NEW, NOT REPLACED 180,000 BTU GAS-FIRED TANKLESS WATER |
| | HEATER TO BE INSTALLED ON THE EXTERIOR OF THE |
| | RESIDENCE. BASED ON WPB BUILDING DEPARTMENT RECORD |
| | PLANS UNDER PERMIT-03061107, THE EXISTING WATER HEATER |
| | IS A 40,000 BTU STORAGE TYPE WATER HEATER INSTALLED ON |
| | THE INTERIOR OF THE RESIDENCE. THE RISER DRAWING |
| | SUBMITTED UNDER PERMIT- 22080050 FOR A GAS-FIRED |
| | GENERATOR SHOWS A 76,000 BTU HEATER INSIDE THE HOUSE. |
| | REFER TO SECS. G2412.3 & G2412.4 FBC RES AND PROVIDE A |
| | COMPLETE GAS RISER FOR THE RESIDENCE THAT INCLUDES THE |
| | FOLLOWING INFORMATION: |
| | |
| | A) DELIVERY PRESSURE AT THE METER. |
| | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | C) TYPES AND SIZES OF PIPING SUPPLYING THE EXISTING |
| | APPLIANCES AND THE NEW WATER HEATER. |
| | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | F) LOCATIONS OF REGULATORS & SHUTOFF VALVES. |
| | G) OUTLET PRESSURES AT REGULATORS. |
| | H) PIPE SIZING TABLES. |
| | |
| | 2) PROVIDE A BASIC FLOOR PLAN DRAWING SHOWING THE |
| | LOCATION OF THE WATER HEATER WITH REQUIRED EXHAUST |
| | OUTLET CLEARANCES TO AIR INTAKES AND OPERABLE OPENINGS |
| | INTO THE BUILDING SUCH AS WINDOWS AND DOORS- SEC. |
| | G2439.1 FBC RES. |
| | CORRECTED PLANS. |
| | |
| | 3) THE PLUMBING PERMIT HAS BEEN CONVERTED A GAS PERMIT. |
| | PLEASE SUBMIT A SUB-PERMIT APPLICATION FOR THE WATER |
| | HEATER- SEC. 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |