| 2023-04-06 19:55:29 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. A WIRING DIAGRAM OF SIGN STILL HAS NOT BEEN |
| | PROVIDED. PLEASE PROVIDE A TYPICAL WIRING DIAGRAM FOR |
| | SIGNS, SHOWING POWER SUPPLY, DISCONNECT, WIRE SIZE, |
| | OVERCURRENT PROTECTION, ETC. FBC 107.2.1 |
| | |
| | 2. THE RESPONSE LETTER SAYS THE ENGINEER OF RECORD HAS |
| | SIGNED ALL PAGES PERTAINING TO ELECTRICAL BUT THEY HAVE |
| | NOT. THE ELECTRICAL SIGN CONTRACTOR HAS DIGITALLY |
| | SIGNED THE PAGES WITH HIS LICENSE NUMBER. AN ELECTRICAL |
| | CONTRACTOR CANNOT TAKE RESPONSIBILITY AND SIGN FOR A |
| | PROJECT THAT IS OVER $125,000 USD. PLEASE SEE FLORIDA |
| | STATUTE 471.003(2)(H). A DESIGN PROFESSIONAL MUST TAKE |
| | RESPONSIBILITY FOR THIS DESIGN. THERE ARE STILL NOTES |
| | ON THE PLAN FROM THE ENGINEER THAT HE DOES NOT TAKE |
| | RESPONSIBILITY FOR ANY ELECTRICAL PORTIONS OF THIS |
| | DESIGN. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |