2022-08-19 11:33:391ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22080704
 8/19/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-2 & P-3: THE HW SYSTEM WILL REQUIRE A
 RECIRCULATION PUMP OR POINT OF USE WATER HEATERS AT THE
 LAVATORIES TO BE IN COMPLIANCE WITH SEC. & TABLE
 C404.5.1 FBC EC- THE1/2-INCH HW SUPPLY PIPES TO THE
 LAVATORIES SHALL BE MAX 2FT. LENGTH FROM THE HOT WATER
 SOURCE.
  
 2) P-1, P-2, & P-3: THE WATER HEATER THERMOSTAT SHALL
 NOT BE THE MEANS OF CONTROLLING THE HOT WATER
 TEMPERATURE. PROVIDE EITHER A MASTER THERMOSTATIC
 MIXING VALVE OR A POINT OF USE VALVE AT THE MOP SINK,
 AND AT SK-1 LOCATIONS IN THE BREAKROOM AND ADMIN. ROOM-
 SEC. 607.1.1 FBC P. PLEASE NOTE THAT ASSE 1070 MIXING
 VALVES ARE APPROVED FOR CONTROLLING TEMPERED WATER
 DELIVERY AT THE LAVATORIES- SEC. 419.4 & 607.1.2.
  
 3) A-1 & A-3.1: SHOW THE 30X48-INCH CLEAR FLOOR SPACE
 DIAGRAM AND DIMENSIONS FOR THE APPROACHES TO THE
 ACCESSIBLE DRINKING FOUNTAIN, THE ALCOVE SINK, AND THE
 ADMIN SINK- SEC. 606.2 FBC ACC.
  
 4) A-1 & A-3.1: SHOW THE KNEE AND TOE CLEARANCES AT THE
 ACCESSIBLE DRINKING FOUNTAIN, THE ALCOVE SINK, AND THE
 ADMIN SINK- SEC. 606.2 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  