| Notes |
| Date |
Text |
| 2022-10-22 16:09:27 | [email protected] | | | [email protected] | | | | | | 1. CONTRACTOR FURNISHED INFORMATION, WHICH ENGINEERED | | | DESIGN PRESSURE REQUIREMENTS ARE BASED ON, STATE LOWEST | | | ELEVATION INSTALLATION TO BE 10'. AS THIS IS A | | | PENTHOUSE WITH 170' MRH, THIS DOES NOT APPEAR TO BE | | | CORRECT DATA. PLEASE VERIFY AND RESUBMIT CORRECTION OR | | | CLARIFICATION. FBC 107.2 | | | 2. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO | | | THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR | | | FBC B 1405.4. | | | DIGITAL SIGNATURE- APPROVED PENDING COMMENT RESPONSE. | | | |
|