Plan Review Notes
Plan Review Notes For Permit 22071422
Permit Number 22071422
Review Stop E
Sequence Number 1
Notes
Date Text
2022-08-05 16:19:43ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL AN OUTDOOR RECEPTACLE(S) TO COMPLY
 WITH NEC 210.52 (E)(1) AND NEC 210. 63
 2) PLEASE DETAIL THE REQUIRED RECEPTACLE IN THE LIVING
 ROOM WITHIN 6 FEET OF THE FRONT DOOR TO COMPLY WITH NEC
 210.52 RECEPTACLE SPACING
 3) PLEASE DETAIL GROUNDING ELECTRODE SYSTEM FOR MAIN
 HOUSE ELECTRIC PANEL TO COMPLY WITH NEC 250.32
 4) PLEASE REMOVE CONFUSING NOTE ON PLANS DETAILING,
 PROPOSED ADDITION, TO MAIN HOUSE, AND HIGHLIGHT NOTE
 STATING, THIS CONSTRUCTION DOCUMENT SET IS FOR GUEST
 HOUSE. FBC 107.2
  
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  