| 2022-09-14 12:37:20 | 1ST REVIEW FMC |
| | PERMIT: 22071347 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SHOW HOW YOU WILL BE PROTECTING THE CORRIDOR |
| | FROM SMOKE. FMC 601.2.1 |
| | |
| | 2) SHEETS M-202 AND M-203: PLEASE SHOW THE REQUIRED |
| | DUCT SMOKE DETECTORS FOR THE REPLACED AHU???S. FMC |
| | 606.2.1 |
| | |
| | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS AND THE |
| | AIR PURIFICATION REDUCTION CALCULATIONS FOR THIS |
| | PROJECT. FBC 107.3.5 |
| | |
| | 4) SHEET M-203: THE FIRE DAMPER FOR VAV-9-02 IS IN THE |
| | WRONG LOCATION, IT IS IN THE CORRIDOR AND NOT AT THE |
| | WALL. PLEASE SHOW THIS FIRE DAMPER IN THE CORRECT |
| | LOCATION. |
| | |
| | 5) SHEET M-203: PLEASE SHOW THE FIRE DAMPER FOR THE 10 |
| | INCH DUCT SUPPLYING AIR TO THE VAV-9-08 AND VAV-9-05 |
| | |
| | 6) PLEASE SHOW THE FIRE DAMPERS WHERE THE MAIN TRUNK |
| | LINES, SUPPLY AND RETURN, FOR AHU-8 AND AHU-9 PENETRATE |
| | THE RATED WALLS AT THE MECHANICAL ROOMS AND CORRIDOR. |
| | FBC 607 |
| | |
| | 7) PLEASE IDENTIFY THE EF-3-1 AND EF-7-1 ON THE |
| | DRAWINGS. FBC 107.3.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |