Plan Review Notes
Plan Review Notes For Permit 22071347
Permit Number 22071347
Review Stop M
Sequence Number 1
Notes
Date Text
2022-09-14 12:37:201ST REVIEW FMC
 PERMIT: 22071347
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW HOW YOU WILL BE PROTECTING THE CORRIDOR
 FROM SMOKE. FMC 601.2.1
  
 2) SHEETS M-202 AND M-203: PLEASE SHOW THE REQUIRED
 DUCT SMOKE DETECTORS FOR THE REPLACED AHU???S. FMC
 606.2.1
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS AND THE
 AIR PURIFICATION REDUCTION CALCULATIONS FOR THIS
 PROJECT. FBC 107.3.5
  
 4) SHEET M-203: THE FIRE DAMPER FOR VAV-9-02 IS IN THE
 WRONG LOCATION, IT IS IN THE CORRIDOR AND NOT AT THE
 WALL. PLEASE SHOW THIS FIRE DAMPER IN THE CORRECT
 LOCATION.
  
 5) SHEET M-203: PLEASE SHOW THE FIRE DAMPER FOR THE 10
 INCH DUCT SUPPLYING AIR TO THE VAV-9-08 AND VAV-9-05
  
 6) PLEASE SHOW THE FIRE DAMPERS WHERE THE MAIN TRUNK
 LINES, SUPPLY AND RETURN, FOR AHU-8 AND AHU-9 PENETRATE
 THE RATED WALLS AT THE MECHANICAL ROOMS AND CORRIDOR.
 FBC 607
  
 7) PLEASE IDENTIFY THE EF-3-1 AND EF-7-1 ON THE
 DRAWINGS. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  