 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) OUTSIDE PORTABLE VAULT IS SUBJECT TO WIND LOADS -
 PLEASE PROVIDE SIGNED AND SEALED VAULT DRAWINGS FROM A
 DESIGN PROFESSIONAL OR PROVIDE STATE APPROVED PRODUCT
 APPROVAL FOR THE VAULT FBC 1609 SEE FBC 107.3
  
 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR THE
 WIND DESIGN FBC 1603.1.4
  
 3) DRAWING A-402 - WIND DESIGN SHOWN RISK CAT. II WIND
 SPEED 168 MPH - WIND SPEED FOR A RISK CAT. II IS 170
 MPH SEE FBC WPB SECTION 120
  
 4) SHOULD THE WIND DESIGN CRITERIA BE - FBC TABLE
 1604.5 RISK CAT. IV WITH WIND SPEED 180 MPH :BUILDINGS
 AND OTHER STRUCTURES HAVING CRITICAL NATIONAL DEFENSE
 FUNCTIONS.
  
 5) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE - FBC
 602.1
  
 6) PLEASE SHOW IF THE BUILDING IS - NON SPRINKLERED OR
 SPRINKLERED.
  
 7) PLEASE SHOW THE PROPOSED RAMP SLOPES - HAND RAILS
 MAY BE REQUIRED - FBC 405.8 HANDRAILS.
 RAMP RUNS WITH A RISE GREATER THAN 6 INCHES (150 MM)
 SHALL HAVE HANDRAILS COMPLYING WITH 505.
  
 8) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE ROOFING SYSTEMS.