| 2023-03-27 08:59:36 | ELECTRIC REVIEW FAILED |
| | |
| | 1) ELECTRIC LOAD CALCULATION IS STILL INCORRECT. ONLY |
| | TWO AC LOADS ARE LISTED AND THREE ARE PRESENT. THERE IS |
| | NO RANGE LOAD LISTED. NO WATER HEATERS ARE LISTED. |
| | THERE ARE CONFLICTS ON DRAWINGS INDICATING A 66 GALLON |
| | ON ONE SHEET AND TWO TANKLESS ON ANOTHER. PLEASE |
| | PROVIDE A CORRECTED CALCULATIO WITH ALL LOADS LISTED. |
| | IN MY EXPERIENCE THE OPTIONAL CALCULATION IS EASIER TO |
| | PROCESS AND ALLOWS A SMALLER DEMAND. |
| | 2) THERE IS STILL NO SMOKE/CARBON ALARM SHOWN ON THE |
| | FIRST FLOOR AS REQUIRED. PLEASE DETAIL THE ALARM AS |
| | REQUIRED |
| | 3) PLEASE PROVIDE AN ACCURATE PANEL SCHEDULE LISTING |
| | ALL LOADS. IE THREE AIR CONDITIONING UNITS, TWO |
| | TANKLESS WATER HEATERS OR THE 66 GALLON. |
| | 4) IF TANKLESS WATER HEATERS ARE TO BE USED, PLEASE |
| | PROVIDE SPECIFICATIONS |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |