Plan Review Notes
Plan Review Notes For Permit 22071340
Permit Number 22071340
Review Stop E
Sequence Number 2
Notes
Date Text
2023-03-27 08:59:36ELECTRIC REVIEW FAILED
  
 1) ELECTRIC LOAD CALCULATION IS STILL INCORRECT. ONLY
 TWO AC LOADS ARE LISTED AND THREE ARE PRESENT. THERE IS
 NO RANGE LOAD LISTED. NO WATER HEATERS ARE LISTED.
 THERE ARE CONFLICTS ON DRAWINGS INDICATING A 66 GALLON
 ON ONE SHEET AND TWO TANKLESS ON ANOTHER. PLEASE
 PROVIDE A CORRECTED CALCULATIO WITH ALL LOADS LISTED.
 IN MY EXPERIENCE THE OPTIONAL CALCULATION IS EASIER TO
 PROCESS AND ALLOWS A SMALLER DEMAND.
 2) THERE IS STILL NO SMOKE/CARBON ALARM SHOWN ON THE
 FIRST FLOOR AS REQUIRED. PLEASE DETAIL THE ALARM AS
 REQUIRED
 3) PLEASE PROVIDE AN ACCURATE PANEL SCHEDULE LISTING
 ALL LOADS. IE THREE AIR CONDITIONING UNITS, TWO
 TANKLESS WATER HEATERS OR THE 66 GALLON.
 4) IF TANKLESS WATER HEATERS ARE TO BE USED, PLEASE
 PROVIDE SPECIFICATIONS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  