| 2023-03-29 11:14:07 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1.) FBC B 107.2.1, ON PLAN SHEET S-3, DETAIL 1 IS |
| | INDICATED ON EAST SIDE OF ROOF. THIS DETAIL NOW |
| | INDICATES WOOD TRUSS RUNNING PARALLEL WITH WALL AND NO |
| | CONNECTION POINT DETAILS TO WALL. AT THE LOCATION |
| | INDICATED (EAST WALL) IT APPEARS THAT THE WOOD TRUSS |
| | ARE RUNNING PERPINDICULAR WITH WALL AND CONNECTION |
| | DETAILS ARE MISSING. PLEASE PROVIDE CONNECTION DETAILS |
| | FOR ALL TRUSS CONNECTIONS INCLUDING THE UPLIFT |
| | REQUIREMENTS AND CAPACITIES AT ALL CONNECTION |
| | LOCATIONS. |
| | |
| | 2.) FBC B 107.2.1, ON PLAN SHEET A-7, DETAIL 1 IS |
| | INDICATED FOR STAIR CANTILEVERED CONNECTION. PLEASE |
| | PROVIDE MORE DETAILS AND SPECIFICATIONS AS TO WALL |
| | CONNECTIONS. |
| | |
| | 3.) FBC B 107.2.1/FBC B 107.3.4.1, PROVIDE PRODUCT |
| | APPROVALS FOR WINDOWS,DOORS, & ROOFING MATERIALS OR |
| | PROVIDE A LIST ON PLANS OF DEFERRED SUBMITTALS. |
| | |
| | 4.) FBC R 401.3, INDICATE ON SITE PLAN/SURVEY THE |
| | ELEVATION & DRAINAGE INDICATORS SHOWING DIRECTION OF |
| | SURFACE WATER TO STORM WATER INLETS. |
| | |
| | NOTE: IT IS HELPFUL TO PROVIDE A RESPONSE SHEET FOR |
| | EACH OF THE PENDING ITEMS. |