Plan Review Notes
Plan Review Notes For Permit 22071340
Permit Number 22071340
Review Stop B
Sequence Number 2
Notes
Date Text
2023-03-29 11:14:07PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, ON PLAN SHEET S-3, DETAIL 1 IS
 INDICATED ON EAST SIDE OF ROOF. THIS DETAIL NOW
 INDICATES WOOD TRUSS RUNNING PARALLEL WITH WALL AND NO
 CONNECTION POINT DETAILS TO WALL. AT THE LOCATION
 INDICATED (EAST WALL) IT APPEARS THAT THE WOOD TRUSS
 ARE RUNNING PERPINDICULAR WITH WALL AND CONNECTION
 DETAILS ARE MISSING. PLEASE PROVIDE CONNECTION DETAILS
 FOR ALL TRUSS CONNECTIONS INCLUDING THE UPLIFT
 REQUIREMENTS AND CAPACITIES AT ALL CONNECTION
 LOCATIONS.
  
 2.) FBC B 107.2.1, ON PLAN SHEET A-7, DETAIL 1 IS
 INDICATED FOR STAIR CANTILEVERED CONNECTION. PLEASE
 PROVIDE MORE DETAILS AND SPECIFICATIONS AS TO WALL
 CONNECTIONS.
  
 3.) FBC B 107.2.1/FBC B 107.3.4.1, PROVIDE PRODUCT
 APPROVALS FOR WINDOWS,DOORS, & ROOFING MATERIALS OR
 PROVIDE A LIST ON PLANS OF DEFERRED SUBMITTALS.
  
 4.) FBC R 401.3, INDICATE ON SITE PLAN/SURVEY THE
 ELEVATION & DRAINAGE INDICATORS SHOWING DIRECTION OF
 SURFACE WATER TO STORM WATER INLETS.
  
 NOTE: IT IS HELPFUL TO PROVIDE A RESPONSE SHEET FOR
 EACH OF THE PENDING ITEMS.