| 2022-10-12 15:14:13 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE PROVIDE AN ELECTRIC RISER. NEC 215.5 |
| | 2) IT APPEARS THE LOAD CACULATION PROVIDED IS INCORRECT |
| | THERE IS NO COOK TOP OR OVEN LISTED. THE WATER HEATER |
| | IS LISTED AS 900VA ON PANEL SCHEDULE AND 4500 ON LOAD |
| | CALCULATION. CAR CHARGER IS LISTED AS 9600 VA ON PANEL |
| | SCHEDULE AND 23000 VA ON LOAD CALCULATION. THERE |
| | APPEARS TO BE 3 AIRCONDITIONING SYSTEMS AND ONLY 2 ARE |
| | LISTED IN THE PANEL SCHEDULES AND LOAD CALCULATION |
| | PLEASE PROVIDE ACCURATE LOAD CALCULATIONS AND PANEL |
| | SCHEDULES. NEC 215.5 AND NEC 220 |
| | 3) PLEASE DETAIL THE REQUIRED CARBON/SMOKE ALARKS AT |
| | THE 1ST LEVEL AND SECOND LEVEL AS REQUIRED PER FBC R |
| | 314 AND 315. CARBON SMOKE ALARMS AT EACH LEVEL AND |
| | WITHIN 10" OF SLEEPING AREAS |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |