Plan Review Notes
Plan Review Notes For Permit 22071340
Permit Number 22071340
Review Stop E
Sequence Number 1
Notes
Date Text
2022-10-12 15:14:13ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE AN ELECTRIC RISER. NEC 215.5
 2) IT APPEARS THE LOAD CACULATION PROVIDED IS INCORRECT
 THERE IS NO COOK TOP OR OVEN LISTED. THE WATER HEATER
 IS LISTED AS 900VA ON PANEL SCHEDULE AND 4500 ON LOAD
 CALCULATION. CAR CHARGER IS LISTED AS 9600 VA ON PANEL
 SCHEDULE AND 23000 VA ON LOAD CALCULATION. THERE
 APPEARS TO BE 3 AIRCONDITIONING SYSTEMS AND ONLY 2 ARE
 LISTED IN THE PANEL SCHEDULES AND LOAD CALCULATION
 PLEASE PROVIDE ACCURATE LOAD CALCULATIONS AND PANEL
 SCHEDULES. NEC 215.5 AND NEC 220
 3) PLEASE DETAIL THE REQUIRED CARBON/SMOKE ALARKS AT
 THE 1ST LEVEL AND SECOND LEVEL AS REQUIRED PER FBC R
 314 AND 315. CARBON SMOKE ALARMS AT EACH LEVEL AND
 WITHIN 10" OF SLEEPING AREAS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER