Plan Review Notes
Plan Review Notes For Permit 22071340
Permit Number 22071340
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-21 11:28:48PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, ON PLAN SHEET S-3, DETAIL 1 IS
 INDICATED ON EAST SIDE OF ROOF. THIS DETAIL INDICATES
 HOLLOW CORE PANELS RUNNING PARALLEL WITH WALL AND NO
 BEARING/CONNECTION POINT TO WALL. AT THE LOCATION
 INDICATED (EAST WALL) IT APPEARS THAT THE HOLLOW CORE
 PANELS ARE RUNNING PERPINDICULAR WITH WALL AND
 BEARING/CONNECTION DETAIL IS MISSING. PLEASE PROVIDE
 DETAIL OR CLARIFICATION.
  
 2.) FBC B 107.2.1, ON PLAN SHEET A-7, DETAIL 1 IS
 INDICATED FOR STAIR CANTILEVERED CONNECTION. PLEASE
 PROVIDE MORE DETAILS AND SPECIFICATIONS AS TO WALL
 CONNECTIONS.
  
 3.) FBC B 107.2.1/FBC B 107.3.4.1, PROVIDE PRODUCT
 APPROVALS FOR WINDOWS,DOORS, & ROOFING MATERIALS OR
 PROVIDE A LIST ON PLANS OF DEFERRED SUBMITTALS.
  
 4.) FBC R 401.3, INDICATE ON SITE PLAN/SURVEY THE
 ELEVATION & DRAINAGE INDICATORS SHOWING DIRECTION OF
 SURFACE WATER TO STORM WATER INLETS.