| Plan Review Notes For Permit 22071340 |
| Permit Number |
22071340 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-21 11:28:48 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, ON PLAN SHEET S-3, DETAIL 1 IS | | | INDICATED ON EAST SIDE OF ROOF. THIS DETAIL INDICATES | | | HOLLOW CORE PANELS RUNNING PARALLEL WITH WALL AND NO | | | BEARING/CONNECTION POINT TO WALL. AT THE LOCATION | | | INDICATED (EAST WALL) IT APPEARS THAT THE HOLLOW CORE | | | PANELS ARE RUNNING PERPINDICULAR WITH WALL AND | | | BEARING/CONNECTION DETAIL IS MISSING. PLEASE PROVIDE | | | DETAIL OR CLARIFICATION. | | | | | | 2.) FBC B 107.2.1, ON PLAN SHEET A-7, DETAIL 1 IS | | | INDICATED FOR STAIR CANTILEVERED CONNECTION. PLEASE | | | PROVIDE MORE DETAILS AND SPECIFICATIONS AS TO WALL | | | CONNECTIONS. | | | | | | 3.) FBC B 107.2.1/FBC B 107.3.4.1, PROVIDE PRODUCT | | | APPROVALS FOR WINDOWS,DOORS, & ROOFING MATERIALS OR | | | PROVIDE A LIST ON PLANS OF DEFERRED SUBMITTALS. | | | | | | 4.) FBC R 401.3, INDICATE ON SITE PLAN/SURVEY THE | | | ELEVATION & DRAINAGE INDICATORS SHOWING DIRECTION OF | | | SURFACE WATER TO STORM WATER INLETS. |
|