| 2022-09-08 16:27:31 | ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING 1 OF 8 SHOWS OCCUPANCY CLASSIFICATION AS |
| | "R3" - SHOULD BE "B" FBC CHAPTER 3 |
| | |
| | 2) PLEASE PROVIDE GUARD RAIL DETAILS - FBC |
| | |
| | 3) PLEASE PROVIDE HAND RAIL DETAILS - FBC |
| | |
| | 4) PLEASE SHOW CEILING HEIGHTS FOR 1ST AND 2ND FLOOR |
| | FBC |
| | |
| | 5) PLEASE SHOW ON THE DRAWINGS THE EXTERIOR WALL AND |
| | CEILING/ROOF SYSTEM INSULATION REQUIREMENTS - PER |
| | ENERGY CALC. |
| | |
| | 6) PLEASE SHOW THE ROOF, EXTERIOR WALL AND FLOOR |
| | SHEATHING TYPE AND THICKNESS - FBC |
| | |
| | 7) PLEASE SHOW THE EXTERIOR CLADDING DETAILS - TYPE, |
| | ATTACHMENTS ETC. - FBC |
| | |
| | 8) PLEASE SHOW EXTERIOR WALL WEATHER PROTECTION - FBC |
| | |
| | 9) PLEASE SHOW JOIST AND GIRDER GUSSET NAILING |
| | REQUIREMENTS - FBC |
| | |
| | 10) DRAWING 8 OF 8 IS MISSING FROM PROJECTDOX. |
| | |
| | 11) PLEASE SHOW THE 2ND FLOOR VERTICAL ACCESSIBLITY - |
| | FBC A 201.1.1 |
| | |
| | 12) PLEASE PROVIDE A SOIL REPORT - FBC |
| | |
| | 13) PLEASE SHOW RESTROOM WALL, FLOOR AND BASE BOARD |
| | FINISHES TO COMPLY WITH FBC |
| | |
| | 14) PLEASE SHOW THE ACCESSIBLE RESTROOM DETAILS PER FBC |
| | ACCESSIBILITY CHAPTER 6 |
| | |
| | 15) PLEASE SHOW THE WALLS SURROUNDING THE SERVICE |
| | SINKS/MOP SINK TO COMPLY WITH - FBC 1210.2.2 |
| | |
| | 16) PLEASE SHOW THE ACCESSIBLE RESTROOM DETAILS PER FBC |
| | ACCESSIBILITY CHAPTER 6 |
| | |
| | 17) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE |
| | ACCESSIBLE PARKING TO THE BUILDING ENTRY - FBC A 202.4 |
| | |
| | |
| | |
| | |