Plan Review Notes
Plan Review Notes For Permit 22071308
Permit Number 22071308
Review Stop P
Sequence Number 1
Notes
Date Text
2022-08-10 11:27:211ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22071308
 8/10/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-2.0A: THE PLAN IS UNACCEPTABLE FOR REVIEW
 BECAUSE IT A MARKED UP, ILLEGIBLE COPY OF THE
 ENGINEER'S SIGNED AND SEALED PLAN SEC. 107.2.1 WPB. THE
 PLAN ALSO SHOWS THE LOCATIONS OF THE G1 & G2
 INTERCEPTORS HAVE BEEN CHANGED FROM THEIR ORIGINAL
 LOCATIONS AT THE SOUTH SIDE OF THE BUILDING AS SHOWN IN
 THE MOST RECENT PLAN REVISION- 3A DATED 6/24/22. THE
 ENGINEER OF RECORD SHALL PROVIDE A DIGITALLY SIGNED AND
 SEALED REVISED PLAN SHOWING THE NEW INTERCEPTOR
 LOCATIONS- SEC. 107.2.1 WPB AND FL. STATUTE 471.025 &
 FAC 61G15-23.005.
  
 2) THE FLORIDA SEPTIC PRODUCT SPECIFICATIONS INDICATING
 COMPLIANCE WITH 2001 FL. PLUMBING CODE AND FAC RULE
 64E-6.013 MARCH 22, 2001 ARE OUTDATED. PLEASE NOTE THE
 ENGINEER OF RECORD HAS SPECIFIED OLD CASTLE
 INTERCEPTORS TO BE INSTALLED AS SHOWN ON SHEET P-0.1
 APPROVED UNDER THE MASTER PERMIT 20120712. PLEASE
 SUBMIT UP-TO-DATE SPECIFICATIONS BEARING THE APPROVAL
 STAMP OF THE ENGINEER OF RECORD- SEC. 107.3.4.1 WPB.
 PLEASE NOTE IN ACCORDANCE WITH SEC.1003.3.7 FBC P- THE
 INTERCEPTOR PRODUCT SPECIFICATIONS SHALL INDICATE THEY
 HAVE BEEN DESIGNED AND TESTED IN ACCORDANCE WITH
 IAPMO/ANSI Z1001.
  
 3) THE ENGINEER OF RECORD SHALL PROVIDE A PIPING
 DIAGRAM FOR THE INTERCEPTORS CONSISTENT WITH SEC. 301.3
 FBC PLUMBING -2020 CODE.THE MARKED UP, OUTDATED
 SPECIFICATIONS SHOWING PIPING INLETS, OUTLETS, AND
 CLEANOUTS ARE UNACCEPTABLE FOR REVIEW- SEC.107.2.1 WPB.
 IN LIEU OF ENGINEERING, THE CONTRACTOR OF RECORD MAY
 SUBMIT A SUPPLEMENTAL PIPING DIAGRAM CLEARLY DRAWN TO
 MINIMUM 1/8-INCH SCALE. THE PLAN SHALL BEAR THE PRINTED
 NAME, LICENSE NUMBER AND SIGNATURE OF THE CONTRACTOR
 AND ALSO THE ADDRESS OF THE PROJECT.
  
 4) SUBMIT ADDITIONAL SPECIFICATIONS FOR THE TRAFFIC
 LIDS THAT BEAR THE NAME OF THE MANUFACTURER AND MODEL
 NUMBER OF THE LIDS. THE SPECS SHALL SHOW THE LIDS FOR
 BOTH THE MANHOLES AND THE SAMPLING PORTS ARE H-20 HEAVY
 DUTY TRAFFIC RATED- SEC. 107.2.1 WPB. THE SPECS SHALL
 BEAR THE APPROVAL STAMP OF THE ENGINEER OF RECORD- SEC.
 107.3.4.1 WPB.
  
 5) PROVIDE SIZING CALCULATIONS FOR THE INTERCEPTORS-
 SEC. 1003.3.7 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  