Plan Review Notes
Plan Review Notes For Permit 22071298
Permit Number 22071298
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-22 17:18:55WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22071298
 ADD: 4047 OKEECHOBEE BLVD. # 200, 201 & 202
 CONT: PBB CONSTRUCTION, LLC
 TEL: 561-767-7681
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 22/2022
 ACTION: DENIED
  
 1) SHEET ALS1.1:
 1A) UNDER THE HEADING BUILDING AREA THE ACTUAL BUILDING
 AREA IS LISTED AS 3,870 SQ. FT. PLEASE REVIEW THE
 EXISTING AND PROPOSED SITE PLAN THE ACTUAL BUILDING
 AREA IS 29,271 SQ. FT. THE TENANT AREA IS 3,870 SQ. FT.
 TYPO PLEASE CORRECT. 107.2.1 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1B) NOTES SECTION 508.3 NONSEPARATED OCCUPANCIES. WORST
 CASE SCENARIO OCCUPANCY WHICH IS S-2 STATED IN PLANS.
 THE LS1.1 AND A1.1.1 FLOOR PLAN ONLY SHOW THE AUTO
 DEALERSHIP SHOWROOM A BUSINESS OCCUPANCY, WHERE IS THE
 S-2 PARKING GARAGE, OPEN OR ENCLOSED?
  
 1C) TABLE 1004.1.2 FLOOR AREA ALLOWABLE PER OCCUPANT.
 PLEASE REFER TO THE 2020 FBC-BUILDING TO UPDATED TABLE
 1004.5.
  
 1D) 2020 FBC-BUILDING TO UPDATED TABLE 1004.5. THE
 OCCUPANT LOAD FACTOR IS NO LONGER 100 BUT 150 SQ. FT./
 OCCUPANT. PLEASE UPDATE PLANS.
  
 1E) THE OCCUPANT LOAD COUNT IS NOT GIVEN CORRECTLY,
 PLUMBING FIXTURE LIST 39 OCCUPANTS, 3870/ 150= 26
 OCCUPANTS. 2020 FBC-BUILDING CODE.
  
 2) SHEET S-4:
 2A) SECTION 1 & SECTION 3 BOTH SHOW NEW ? X 10 ?X10?
 BASE PLATE, VERTICAL HSS 4X4X1/4 TUBING, AND W12X19
 STEEL BEAM, THE PLANS DO NOT PROVIDE TYPE OF WELDS NOR
 SIZE OF WELDS?
 2020 FBC-BUILDING CODE 2204.1.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2B) WELDED OR BOLTED CONNECTIONS. THIS BUILDING
 CONTAINS EITHER BOLTED AND OR WELDED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 3) ROOFING PRODUCT APPROVAL FL. 2948-R15 WAS SUBMITTED.
 PAGE 2 OF 49 TABLE 2A CIRCLED, STEEL OR CONCRETE
 DECKING, NEW, REROOF (TEAR-OFF) OR RECOVER TYPE B-1
 MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP
 INSULATION, BONDED COVER SHEET PAGES THESE SYSTEMS ARE
 ON 10-14, APPENDIX PAGE 1 OF 49.
 SHEET 4 OF 49 HEADING MEMBRANE/ ADHESIVE COMBINATION,
 MATERIAL ARE HIGHLIGHTED. BUT PAGE 9 OF 49 FOR WOOD
 DECKS WAS CIRCLED AND HIGHLIGHTED, - 60.0 VASD. THE
 WOOD SYSTEM DOES ALLOW FOR INCREASED FASTENING IN ROOF
 ZONES 2 & 3 AS PER RAS 117. MISSING PAGES 10-14 FOR
 STEEL DECKING AND ANCHOR FASTENING, WE DO NOT KNOW
 ALLOWABLE PRESSURES, MISSING PAGES AND IF INCREASE
 FASTENING IS ALLOWED.
  
 4) NOA 21-1216.10 TRULITE 3100 WINDOW WALL SYSTEM LMI.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  