| Date |
Text |
| 2022-08-22 17:18:55 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22071298 |
| | ADD: 4047 OKEECHOBEE BLVD. # 200, 201 & 202 |
| | CONT: PBB CONSTRUCTION, LLC |
| | TEL: 561-767-7681 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. AUGUST 22/2022 |
| | ACTION: DENIED |
| | |
| | 1) SHEET ALS1.1: |
| | 1A) UNDER THE HEADING BUILDING AREA THE ACTUAL BUILDING |
| | AREA IS LISTED AS 3,870 SQ. FT. PLEASE REVIEW THE |
| | EXISTING AND PROPOSED SITE PLAN THE ACTUAL BUILDING |
| | AREA IS 29,271 SQ. FT. THE TENANT AREA IS 3,870 SQ. FT. |
| | TYPO PLEASE CORRECT. 107.2.1 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 1B) NOTES SECTION 508.3 NONSEPARATED OCCUPANCIES. WORST |
| | CASE SCENARIO OCCUPANCY WHICH IS S-2 STATED IN PLANS. |
| | THE LS1.1 AND A1.1.1 FLOOR PLAN ONLY SHOW THE AUTO |
| | DEALERSHIP SHOWROOM A BUSINESS OCCUPANCY, WHERE IS THE |
| | S-2 PARKING GARAGE, OPEN OR ENCLOSED? |
| | |
| | 1C) TABLE 1004.1.2 FLOOR AREA ALLOWABLE PER OCCUPANT. |
| | PLEASE REFER TO THE 2020 FBC-BUILDING TO UPDATED TABLE |
| | 1004.5. |
| | |
| | 1D) 2020 FBC-BUILDING TO UPDATED TABLE 1004.5. THE |
| | OCCUPANT LOAD FACTOR IS NO LONGER 100 BUT 150 SQ. FT./ |
| | OCCUPANT. PLEASE UPDATE PLANS. |
| | |
| | 1E) THE OCCUPANT LOAD COUNT IS NOT GIVEN CORRECTLY, |
| | PLUMBING FIXTURE LIST 39 OCCUPANTS, 3870/ 150= 26 |
| | OCCUPANTS. 2020 FBC-BUILDING CODE. |
| | |
| | 2) SHEET S-4: |
| | 2A) SECTION 1 & SECTION 3 BOTH SHOW NEW ? X 10 ?X10? |
| | BASE PLATE, VERTICAL HSS 4X4X1/4 TUBING, AND W12X19 |
| | STEEL BEAM, THE PLANS DO NOT PROVIDE TYPE OF WELDS NOR |
| | SIZE OF WELDS? |
| | 2020 FBC-BUILDING CODE 2204.1. |
| | 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 2B) WELDED OR BOLTED CONNECTIONS. THIS BUILDING |
| | CONTAINS EITHER BOLTED AND OR WELDED CONNECTIONS. THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE ACTING CHIEF BUILDING INSPECTOR |
| | RICHARD BRUNELLE AT 561-805-6670. |
| | |
| | 3) ROOFING PRODUCT APPROVAL FL. 2948-R15 WAS SUBMITTED. |
| | PAGE 2 OF 49 TABLE 2A CIRCLED, STEEL OR CONCRETE |
| | DECKING, NEW, REROOF (TEAR-OFF) OR RECOVER TYPE B-1 |
| | MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP |
| | INSULATION, BONDED COVER SHEET PAGES THESE SYSTEMS ARE |
| | ON 10-14, APPENDIX PAGE 1 OF 49. |
| | SHEET 4 OF 49 HEADING MEMBRANE/ ADHESIVE COMBINATION, |
| | MATERIAL ARE HIGHLIGHTED. BUT PAGE 9 OF 49 FOR WOOD |
| | DECKS WAS CIRCLED AND HIGHLIGHTED, - 60.0 VASD. THE |
| | WOOD SYSTEM DOES ALLOW FOR INCREASED FASTENING IN ROOF |
| | ZONES 2 & 3 AS PER RAS 117. MISSING PAGES 10-14 FOR |
| | STEEL DECKING AND ANCHOR FASTENING, WE DO NOT KNOW |
| | ALLOWABLE PRESSURES, MISSING PAGES AND IF INCREASE |
| | FASTENING IS ALLOWED. |
| | |
| | 4) NOA 21-1216.10 TRULITE 3100 WINDOW WALL SYSTEM LMI. |
| | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| | OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |