| Plan Review Notes For Permit 22071281 |
| Permit Number |
22071281 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-24 16:05:25 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SCOPE OF WORK DOES NOT SPECIFY IF THE EXISTING | | | ROOFING MATERIALS ARE BEING REMOVED OR ROOFED OVER. | | | CLARIFY. FBC 107.2.1 | | | | | | 2) THE FL COVER SHEET IS MISSING FROM THE METAL ROOF | | | PRODUCT APPROVAL. FBC 107.2.1 | | | | | | 3) SPECIFY WHICH ONE OF THE UNDERLAYMENTS REQUIRED BY | | | FBC-R 1507.1.1.1 WILL BE USED FOR THIS PROJECT. IF A | | | SELF-ADHERING UNDERLAYMENT PRODUCT IS TO BE INSTALLED, | | | SUBMIT IT'S PRODUCT APPROVAL. FBC AMENDMENTS 107.3.4 | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|