Plan Review Notes
Plan Review Notes For Permit 22071261
Permit Number 22071261
Review Stop SIGNATURE
Sequence Number 1
Notes
Date Text
2022-08-15 07:32:50SIGNATURE REVIEW
 PERMIT- 22071261
 8/15/2022
  
 1) THE IRRIGATION PLANS (IR-1 & 2) SHALL BEAR THE
 DIGITAL SIGNATURE AND SEAL OF THE ENGINEER OF RECORD-
 SEC. 471.025 AND SEC. 61G15-23.005 FLORIDA
 ADMINISTRATIVE CODE. PLANS AND DETAILS SUBMITTED
 ELECTRONICALLY SHALL BEAR DIGITAL SIGNATURES AND SEALS-
 SEE FBPE GUIDELINES BELOW.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved