| 2022-12-02 14:22:19 | 5TH REVIEW FMC |
| | PERMIT: 22071259 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) I AM STILL TRYING TO GET THE ANSWER TO COMMENT 1 OF |
| | PREVIOUS REVIEW CYCLE. THE PERMIT NUMBER THAT WAS GIVEN |
| | IN REFERENCE TO SHEET A8.0.1 IS THIS PERMIT NUMBER. |
| | THERE ARE NO A SHEETS IN THIS SUBMITTAL AND THERE ARE A |
| | LOT OF A SHEETS FOR THIS BUILDING, A LOT FOR EACH |
| | PERMIT FOR THIS BUILDING AND BUILDOUTS. I AM ASKING FOR |
| | YOU TO EITHER SUBMIT SHEET A8.0.1 AS A REFERENCE ONLY |
| | SHEET OR TELL ME THE PERMIT NUMBER OF THE A.8.0.1 THAT |
| | YOU ARE REFERENCING SO I CAN FIND IT MYSELF. |
| | |
| | 2) THE LETTER SUBMITTED FROM MR. ERIC CHAPA FROM |
| | CAPTIVEAIRE ONLY STATES WHAT THE FMC STATES: SUCH ROOM |
| | OR SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE |
| | FAN MANUFACTURERS INSTALLATION INSTRUCTIONS. PLEASE |
| | PROVIDE THIS INFORMATION FROM THE FAN MANUFACTURER. THE |
| | REVISED DRAWING REFERENCES NOTE 10 (COOLING TUBE TO |
| | MOTOR COMPARTMENT, BOTH SIDES) PLEASE PROVIDE A DETAIL |
| | DRAWING OF THIS. PLEASE PROVIDE THE INSTALLATION |
| | INSTRUCTIONS FOR THE GREASE DUCT IN-LINE FAN. FMC |
| | 506.5.1.2 |
| | |
| | 3) PLEASE SUBMIT A REVISION FOR THE NEW PIZZA OVENS AND |
| | THE DUCTWORK THAT IS NOW ON THE NEW SHEETS ADDED TO |
| | THIS SUBMITTAL; MKH-502 AND MKH-503, INCLUDE THE ADDED |
| | VALUE TO THIS REVISION. |
| | |
| | 4) PROVIDE A DESIGN FOR THE PIZZA OVENS DUCTWORK. IS |
| | THE DUCTWORK FOR THESE PIZZA OVEN TO BE FIRE WRAPPED? |
| | FBC 107.3.5 |
| | |
| | 5) PROVIDE SPECS FOR THE PIZZA OVENS THAT ARE SHOWN ON |
| | THE NEW SHEETS MKH-502 AND MKH-503 ALSO PROVIDE |
| | INFORMATION FOR THE DUCT WORK FOR THESE 2 PIZZA OVENS. |
| | THE KITCHEN FAN SCHEDULE LISTED ON MKH-503 INDICATES |
| | THE DUCT SIZE CONNECTION AS 6 INCH BUT THE DUCTWORK |
| | SHOWN ON MKH-502 INDICATES THE DUCTWORK TO BE 8 INCH. |
| | PLEASE EXPLAIN? |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |