2022-11-03 16:09:451ST REVIEW FMC
 PERMIT: 22071259
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE PERMIT NUMBER FOR THIS A8.0.1
 THAT IS REFERENCED IN THE RESPONSE LETTER. IF THIS
 ENCLOSURE IS LOCATED IN A PLENUM IT CANNOT BE ALLOWED
 TO ???BREATHE WITH THE PLENUM AIR.??? THE IN LINE FAN
 WILL NEED TO MEET THE REQUIREMENTS OF FMC 506.5.1.2
  
 506.5.1.2 IN-LINE FAN LOCATION. WHERE ENCLOSED DUCT
 SYSTEMS ARE CONNECTED TO IN-LINE FANS NOT LOCATED
 OUTDOORS,
 THE FAN SHALL BE LOCATED IN A ROOM OR SPACE HAVING THE
 SAME FIRE-RESISTANCE RATING AS THE DUCT ENCLOSURE.
 ACCESS SHALL BE PROVIDED FOR SERVICING AND CLEANING OF
 FAN COMPONENTS. SUCH ROOMS OR SPACES SHALL BE
 VENTILATED
 IN ACCORDANCE WITH THE FAN MANUFACTURER???S
 INSTALLATION INSTRUCTIONS.
  
 2) PROVIDE THE DOCUMENT THAT SHOWS THE TENANT ACCESS
 AGREEMENT FMC 306.1
  