| 2022-09-07 12:55:55 | 2ND REVIEW FMC |
| | PERMIT: 22071259 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | DRAWING 3 OF 4: KITCHEN HOOD EXHAUST FAN 2 HOUR RATED |
| | SHAFT DETAIL: |
| | |
| | 1) PLEASE PROVIDE A MORE DETAILED DRAWING OF THIS RATED |
| | BOX THAT WILL ENCLOSE THE KEF-1. EXPLAIN WHY THE FIRE |
| | DAMPERS ARE IN THIS DESIGN. PROVIDE THE ARCHITECTURAL |
| | SHEETS CALLED OUT IN NOTE 1. NOTE 2, PROVIDE A DETAIL |
| | DRAWING OF THIS ACCESS DOOR. NOTE 8 STATES THE 2-HOUR |
| | FIRE WRAP SHALL TERMINATE TO 2- HOUR GYPSUM BOARD |
| | ENCLOSURE BUT THE INSTALLATION DETAIL FOR TRANSITION TO |
| | RATED SHAFT DETAIL DOES NOT SHOW THIS. PLEASE PRESENT |
| | CONSISTENT DETAILS. THE INSTALLATION DETAIL FOR |
| | TRANSITION TO RATED SHAFT DETAIL DOES NOT SHOW THAT |
| | NOTE 5 IS BEING USED, SHOW THE BANDING OR REMOVE THIS |
| | NOTE 5. THERE IS A 6 ON THE DESIGN DRAWING BUT THIS |
| | NUMBER 6 IS NOT LISTED, EXPLAIN WHAT THIS 6 IS |
| | REFERENCING. FBC107.3.5 |
| | |
| | 2) ACCORDING TO THIS DESIGN FOR THE HOOD EXHAUST AND |
| | DISHWASHER EXHAUST, THE DUCTWORK IS TRAVELING THROUGH A |
| | FUTURE TENANT SPACE, MEDICAL OFFICE, PLEASE EXPLAIN HOW |
| | THIS GREASE DUCT WILL BE ACCESSIBLE FOR CLEANING AND |
| | MAINTAINING. FBC 107.3.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |