Plan Review Notes
Plan Review Notes For Permit 22071259
Permit Number 22071259
Review Stop M
Sequence Number 2
Notes
Date Text
2022-09-07 12:55:552ND REVIEW FMC
 PERMIT: 22071259
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 DRAWING 3 OF 4: KITCHEN HOOD EXHAUST FAN 2 HOUR RATED
 SHAFT DETAIL:
  
 1) PLEASE PROVIDE A MORE DETAILED DRAWING OF THIS RATED
 BOX THAT WILL ENCLOSE THE KEF-1. EXPLAIN WHY THE FIRE
 DAMPERS ARE IN THIS DESIGN. PROVIDE THE ARCHITECTURAL
 SHEETS CALLED OUT IN NOTE 1. NOTE 2, PROVIDE A DETAIL
 DRAWING OF THIS ACCESS DOOR. NOTE 8 STATES THE 2-HOUR
 FIRE WRAP SHALL TERMINATE TO 2- HOUR GYPSUM BOARD
 ENCLOSURE BUT THE INSTALLATION DETAIL FOR TRANSITION TO
 RATED SHAFT DETAIL DOES NOT SHOW THIS. PLEASE PRESENT
 CONSISTENT DETAILS. THE INSTALLATION DETAIL FOR
 TRANSITION TO RATED SHAFT DETAIL DOES NOT SHOW THAT
 NOTE 5 IS BEING USED, SHOW THE BANDING OR REMOVE THIS
 NOTE 5. THERE IS A 6 ON THE DESIGN DRAWING BUT THIS
 NUMBER 6 IS NOT LISTED, EXPLAIN WHAT THIS 6 IS
 REFERENCING. FBC107.3.5
  
 2) ACCORDING TO THIS DESIGN FOR THE HOOD EXHAUST AND
 DISHWASHER EXHAUST, THE DUCTWORK IS TRAVELING THROUGH A
 FUTURE TENANT SPACE, MEDICAL OFFICE, PLEASE EXPLAIN HOW
 THIS GREASE DUCT WILL BE ACCESSIBLE FOR CLEANING AND
 MAINTAINING. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  