| Plan Review Notes For Permit 22071251 |
| Permit Number |
22071251 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-01 11:08:13 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT THE TEST REPORTS FOR THE PROPOSED | | | UNDERLAYMENT BASED ON THE EXISTING SITE CONDITIONS. | | | TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: | | | E-84, E-90 & E-492. | | | FBC 603.1 FLAME SPREAD - ASTM E 84-09 | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 WALLS, | | | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR | | | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E | | | 90. | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | |
|