| Notes |
| Date |
Text |
| 2022-08-31 09:24:52 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE POOL EQUIPMENT IS REQUIRED TO BE ANCHORED TO | | | RESIST WINDLOADS AND FLOOD WATER FORCES. SPECIFY THE | | | FASTNER TYPE, SIZE, LOCATIONS AND EMBED DEPTHS. | | | FBC-R301 | | | | | | 2) THE PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA. THE POOL EQUIPMENT IS REQUIRED TO COMPLY WITH | | | FBC-R 322.1.6. EQUIPMENT FOR POOLS, SPAS AND WATER | | | FEATURES SHALL BE PERMITTED BELOW THE ELEVATION | | | REQUIRED IN SECTION R322.2 OR R322.3 PROVIDED IT IS | | | ELEVATED TO THE EXTENT PRACTICAL, IS ANCHORED TO | | | PREVENT FLOTATION AND RESIST FLOOD FORCES, AND IS | | | SUPPLIED BY BRANCH CIRCUITS THAT HAVE GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION. |
|