| Plan Review Notes For Permit 22071205 |
| Permit Number |
22071205 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-02 17:23:43 | ELECTRICAL PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | | CIRCUIT. NEC 250; FBC RE 3607.3. | | | SEE ELECTRICAL NOTE #6 ON PLAN PAGE MEP-1. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|