| 2022-07-27 11:55:42 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND - 107.3.5 - THE SITE PLAN YOU | | | SUBMITTED SHOWS THE LOCATION OF THE BACKFLOW IN THE | | | WRONG SPOT. | | | | | | 2. 2017 WPB AMEND - 107.3.5 - THE SPECS YOU'VE | | | SUBMITTED SHOW A BACKFLOW THAT IS NON-COMPLIANT. IT | | | STATES IN THE SPECS, "IT IS ILLEGAL TO USE THIS PRODUCT | | | IN ANY PLUMBING SYSTEM PROVIDING WATER FOR HUMAN | | | CONSUMPTION, ...ETC." PLEASE PROVIDE A SPEC SHEET FOR | | | THE ONE THAT IS ACTUALLY INSTALLED ALREADY ON THE JOB. | | | IT SHOULD CLEARLY STATE SOMEWHERE ON THE SHEET THAT IT | | | IS "LEAD FREE". | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|