| Date |
Text |
| 2022-08-03 07:55:59 | 2ND GAS REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. NOT ADDRESSED - 2017 WPB AMEND - 107.3 - THE |
| | GENERATOR WILL REQUIRE A SEPARATE PERMIT. PLEASE MARK |
| | THIS AS A "FUTURE GENERATOR". IT SHOULD BE NOTED THAT |
| | THE "FUTURE GENERATOR" WILL NEED 10 FOOT SETBACKS FROM |
| | OPENINGS INTO THE STRUCTURE. |
| | |
| | 2. NOT ADDRESSED - 2017 WPB AMEND 107.3.5.3 (13) - SHOW |
| | THE COMBUSTION AIR CALCS FOR THE DRYER INSTALLATION AND |
| | PROVIDE MAKEUP AIR IF REQUIRED. |
| | |
| | 3. NOT ADDRESSED. THE POOL PERMIT INDICATES A HEAT |
| | PUMP. IN ORDER TO DO A GAS HEATER, A REVISION OR A |
| | SEPARATE PERMIT IS REQUIRED. -- 2017 WPB AMEND - 107.3 |
| | - THE POOL HEATER WILL REQUIRED A SEPARATE PERMIT. |
| | PLEASE INDICATE ON PLANS. |
| | |
| | 4. THE DRAWING SEEMS TO INDICATE THE WATER HEATER IS |
| | INDOORS AND THE SPECS SHOW AN OUTDOOR UNIT - CLARIFY |
| | THE DRAWING OR CHANGE THE SPECS. IF IT IS AN INDOOR |
| | UNIT, SHOW THE VENTING AND/OR COMBUSTION AIR CALCS. |
| | 2017 WPB AMEND 107.3.5.3 (13) - SHOW THE LOCATION OF |
| | THE WATER HEATER ON A FLOOR PLAN AND, IF INDOORS, SHOW |
| | THE COMBUSTION AIR CALCS. |
| | |
| | 5. DONE |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |