| 2022-07-28 08:53:42 | 1ST GAS REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND ? 107.3 - THE GENERATOR WILL REQUIRE |
| | A SEPARATE PERMIT. PLEASE MARK THIS AS A "FUTURE |
| | GENERATOR". IT SHOULD BE NOTED THAT THE "FUTURE |
| | GENERATOR" WILL NEED 10 FOOT SETBACKS FROM OPENINGS |
| | INTO THE STRUCTURE. |
| | |
| | 2. 2017 WPB AMEND 107.3.5.3 (13) - SHOW THE COMBUSTION |
| | AIR CALCS FOR THE DRYER INSTALLATION AND PROVIDE MAKEUP |
| | AIR IF REQUIRED. |
| | |
| | 3. 2017 WPB AMEND ? 107.3 - THE POOL HEATER WILL |
| | REQUIRED A SEPARATE PERMIT. PLEASE INDICATE ON PLANS. |
| | |
| | 4. 2017 WPB AMEND 107.3.5.3 (13) - SHOW THE LOCATION OF |
| | THE WATER HEATER ON A FLOOR PLAN AND, IF INDOORS, SHOW |
| | THE COMBUSTION AIR CALCS. |
| | |
| | 5. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SHOW THE LINE |
| | PRESSURES ON THE GAS LINE THAT YOU USED FOR SIZING THE |
| | GAS PIPE. ALSO, INDICATE THE LENGHTS OR THE RUNS THAT |
| | WERE USED FOR THE SIZING OF THE GAS LINE. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |