| 2023-04-18 15:09:28 | PLEASE ADDRESS EACH COMMENT MENTIONED BELOW ON THE |
| | DRAWINGS. |
| | WHAT IS GOING TO HAPPEN WITH THE AHU-1 AND AHU-2 WITH |
| | ITHIS DESIGN? |
| | THIS NEW DESIGN SHOWS A SPLIT SYSTEM AIR CONDITIONERS |
| | DETAIL 2/H1. THIS DETAIL SPECIFIES 6- 25 TONS COOLING |
| | UNITS AND 5-25 TONS AIR HANDLERS. WHERE ARE THESE TO BE |
| | USED IN THIS PROJECT? |
| | 1ST REVIEW FMC |
| | PERMIT: 22071171 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | IT APPEARS THERE IS A L9OT OF CHANGES FROM THE ORIGINAL |
| | SUBMITTAL PERMIT NUMBER 21030310. PLEASE RESPOND TO THE |
| | FOLLOWING REVIEW COMMENTS FOR THIS REVISED DESIGN. |
| | |
| | 1) PROVIDE THE CORRECT VALUE OF WORK ON THE APPLICATION |
| | FOR THIS NEW SYSTEM. |
| | |
| | 2) PROVIDE A NARRATIVE TELLING THE SCOPE OF WORK FOR |
| | THIS REVISED DESIGN. FBC 107.3.5 |
| | |
| | 3) THE ORIGINAL DESIGN WAS FOR 3 EXISTING AHUS. THIS |
| | LATEST SUBMITTAL IS NOW SPECIFYING 6-25 TONS COOLING |
| | UNITS AND 5-25 TONS AIR HANDLING UNITS. |
| | |
| | 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THESE NEW |
| | SYSTEMS. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |