| Plan Review Notes For Permit 22071171 |
| Permit Number |
22071171 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2023-03-14 09:46:01 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING 10/12 SHOWS 2ND FLOOR AS "TRAINING AREA" - | | | PLEASE PROVIDE VERTICAL ACCESSIBILITY FOR THE ASSEMBLY | | | AREA - FBC A 201.1.1 | | | | | | 2) DRAWING 3/12 --- 4/12 ----- AND 10/12 SHOWS | | | CONSTRUCTION TYPE AS TYPE II - CANNOT HAVE WOOD FRAMING | | | BEARING WALLS AND WOOD FLOOR FRAMING IN A BUILDING OF | | | TYPE II CONSTRUCTION - SEE FBC 603.1 | | | |
|