| 2023-03-13 13:47:01 | 1ST REVIEW FMC | | | PERMIT: 22071171 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | IT APPEARS THERE IS A L9OT OF CHANGES FROM THE ORIGINAL | | | SUBMITTAL PERMIT NUMBER 21030310. PLEASE RESPOND TO THE | | | FOLLOWING REVIEW COMMENTS FOR THIS REVISED DESIGN. | | | | | | 1) PROVIDE THE CORRECT VALUE OF WORK ON THE APPLICATION | | | FOR THIS NEW SYSTEM. | | | | | | 2) PROVIDE A NARRATIVE TELLING THE SCOPE OF WORK FOR | | | THIS REVISED DESIGN. FBC 107.3.5 | | | | | | 3) THE ORIGINAL DESIGN WAS FOR 3 EXISTING AHUS. THIS | | | LATEST SUBMITTAL IS NOW SPECIFYING 6-25 TONS COOLING | | | UNITS AND 5-25 TONS AIR HANDLING UNITS. | | | | | | 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THESE NEW | | | SYSTEMS. | | | | | | 5) WHERE IS THE CONDENSING UNITS GOING TO BE LOCATED? | | | SHOW THIS ON THE DRAWING. FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|