| Plan Review Notes For Permit 22071171 |
| Permit Number |
22071171 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2023-01-27 11:01:56 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING 8/12 SHOWS 2ND FLOOR AS "TRAINING AREA" - | | | PLEASE PROVIDE VERTICAL ACCESSIBILITY FOR THE ASSEMBLY | | | AREA - FBC A 201.1.1 | | | | | | 2) DRAWING 7/12 SHOWS 2ND FLOOR AS "TRAINING AREA" - | | | PLEASE PROVIDE VERTICAL ACCESSIBILITY FOR THE ASSEMBLY | | | AREA - FBC A 201.1.1 | | | | | | 3) DRAWING 5/12 PLEASE SHOW THE HAND RAIL EXTENSIONS ON | | | THE HAND RAIL NOT THE GUARDRAIL. - FBC 1014.6 | | | | | | 4) DRAWING 3/12 SHOWS CONSTRUCTION TYPE AS TYPE II - | | | CANNOT HAVE WOOD FRAMING BEARING WALLS AND WOOD FLOOR | | | FRAMING IN A BUILDING OF TYPE II CONSTRUCTION - SEE FBC | | | 603.1 | | | |
|