Plan Review Notes
Plan Review Notes For Permit 22071171
Permit Number 22071171
Review Stop E
Sequence Number 3
Notes
Date Text
2023-04-17 11:16:59ELECTRIC REVIEW FAILED
 1) IT APPEARS THIS REVISION IS TO INCLUDE CHANGING THE
 AIR CONDITIONING SYSTEM. THE AIR CONDITIONING SYSTEM IS
 STATED AS BEING 3 PHASE, HOWEVER, THE ELECTRICAL PANEL
 SCHEDULE IS LISTED AS A 1 PHASE SYSTEM. PLEASE CORRECT
 CONFLICTS AS APPLICABLE. IN ADDITION PLEASE PROVIDE AN
 UPDATED ELECTRIC RISER DIAGRAM TO INCLUDE ELECTRICAL
 PANEL, DISCONNECT, CONDUIT, CONDUCTOR AND OVERCURRENT
 PROTECTION SIZES. IN ADDITION, INCLUDE A PANEL SCHEDULE
 DETAILING ALL ELECTRIC LOADS AND OVERCURRENT PROTECTION
 SIZES. ALSO INCLUDE AN ACCURATE ELECTRIC LOAD
 CALCULATION. NEC 215.5, NEC 215.2, NEC 220 FBC 107.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  