| 2023-04-17 11:16:59 | ELECTRIC REVIEW FAILED | | | 1) IT APPEARS THIS REVISION IS TO INCLUDE CHANGING THE | | | AIR CONDITIONING SYSTEM. THE AIR CONDITIONING SYSTEM IS | | | STATED AS BEING 3 PHASE, HOWEVER, THE ELECTRICAL PANEL | | | SCHEDULE IS LISTED AS A 1 PHASE SYSTEM. PLEASE CORRECT | | | CONFLICTS AS APPLICABLE. IN ADDITION PLEASE PROVIDE AN | | | UPDATED ELECTRIC RISER DIAGRAM TO INCLUDE ELECTRICAL | | | PANEL, DISCONNECT, CONDUIT, CONDUCTOR AND OVERCURRENT | | | PROTECTION SIZES. IN ADDITION, INCLUDE A PANEL SCHEDULE | | | DETAILING ALL ELECTRIC LOADS AND OVERCURRENT PROTECTION | | | SIZES. ALSO INCLUDE AN ACCURATE ELECTRIC LOAD | | | CALCULATION. NEC 215.5, NEC 215.2, NEC 220 FBC 107.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | | | | |
|